121
Description
Test Standard
Mode
Group
Test Level
IEC 61000-4-3:2010
6 Faces Enclosure ports
Level 4 : 30V/m (rms)
Frequency sweep:
from 800MHz to 960MHz
from 1400MHz to 2000MHz
Electrostatic Discharge
IEC 61000-4-2:2008
IEC 60255-26:2013
Enclosure ports
Level 4:
15kV air discharge.
8kV contact discharge.
Surge Immunity
IEC 61000-4-5:2014
IEC 60255-26:2013
DM
AC/DC Power, Alarm,
binary Input/Output
Ports
Level 3:
Source impedance 2Ω, Line
-to-
line 2kV,
coupling resistor 0Ω, coupling
capacitance 18 µF
CM
Level 4:
Source impedance 2Ω, Line
-to-
earth 4kV,
coupling resistor 10Ω, coupling
capacitance 9 µF
DM
Signal ports
Level 4:
Source impedance 2Ω, Line
-to-
ground 4kV,
coupling resistor 40Ω, coupling
capacitance 0,5 µF
Power frequency magnetic
field
IEC 61000-4-8:2009
IEC 60255-26:2013
Enclosure port
Level 5:
100A/m continuous (≥60s)
1000A/m for 1s
Pulsed magnetic field
immunity
IEC 61000-4-9:2001
Enclosure port
Level 5:
1000A/m peak
Applied 6.4/16µs magnetic field
pulses in all planes for the EUT
in a quiescent state.
Damped oscillatory
magnetic field immunity
IEC 61000-4-10:2001 - 11
Enclosure port
Level 5:
100A/m peak
Applied in all planes at:
100kHz, repetition rate ≥ 40Hz,
during 60s
1MHz, repetition rate ≥ 400Hz,
during 60s
Slow damped oscillatory
wave
IEC 61000-4-18:2011
IEC 60255-26:2013
CM
DC and AC Power
Level 3:
2.5kV @100kHz and 1MHz
DM
DC and AC Power
Level 3:
1kV peak voltage @100kHz and
1MHz
CM
Ethernet ports
Level 3:
2.5kV @100kHz and 1MHz
Summary of Contents for Reason H49