C0047ENb
Good conductor surface
Cable crimp
Copper cable
minimum section: 2.5mm²
Figure 21: Example of Earth Cable
6.2.2
Casing / Earth Interconnection
To protect against disturbances, each Reason H49 must be carefully and correctly
interconnected.
Within Reason H49 equipment, earth and casing must be connected to a grid-like
grounding system in the shortest possible way using low impedance (at high
frequencies), wide and short electrical connections (wires or braids) as specified in
the IEC 61000-5 standard.
S1645ENa
1,5 cm
1,5 cm
1,5 cm
1,5 cm
Figure 22: Recommended mounting and Casing / Earth interconnection