Derived measurements are continuously recorded. A new record is created at each
hour rollover. The record size depends on the number of derived measurements
selected by the user (limited to 64).
By trigger:
The disturbance recorder can be triggered by a Boolean equation, by a cross-trigger
signal of another recorder, by a manual trigger using the Web Interface, or by the
triggering of the fault recorder. It is possible to select the derived quantity of
triggered disturbance records. If the quantities are not manually selected, the record
will consist of all the quantities available for measurement. The record size depends
of the number of derived measurements selected by the user.
Continuous and triggered disturbance records share the same mass storage area.
2.1
Recorded Values
The following values are recorded by the continuous and triggered disturbance
recorders:
RMS value of voltage and current circuits;
Voltage and current phasors;
Frequency of voltage circuits;
Positive sequence of voltage and current circuits;
Negative sequence of voltage and current circuits;
Imbalance of voltage and current circuits;
Total harmonic distortion of voltage and current circuits;
Apparent combined power of power circuits;
Apparent fundamental power of power circuits;
Active fundamental power of power circuits;
Reactive fundamental power of power circuits;
Digital channels (state of digital inputs and binary GOOSE messages).
2.2
Recording Times by Trigger
Once triggered, the following parameters are considered by the disturbance
recorder:
Parameter
Allowed values
Increment
Pre-fault time (
𝑡
pre
)
0 … 5 min
0.1 min
Post-fault time (
𝑡
pos
)
0 … 20 min
0.1 min
Maximum Record
time
(
𝑡
max
)
1 … 20 min
0.1 s
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...