RPV311
Chapter 13
– RPV Manager
RPV311-TM-EN-7
198
Figure 95: Polling configuration
Polling Configuration fields description:
COMTRADE Directory:
directory path where the new records are downloaded and
where the fault locator calculation searches.
Display Downloaded COMTRADES Limit:
maximum COMTRADE records already
downloaded that will be displayed on the screen
Display Available COMTRADE Age (day):
limit, in days, of downloaded records that
will be fetched and displayed on the screen.
COMTRADE DAT File:
format in which the COMTRADE file will be saved.
Start Auto Polling on Init:
starts Auto Polling automatically by the application.
Automatic Fault Location:
performs the fault location calculation after the
COMTRADE file refresh.
Auto Refresh Interval (min):
interval, in minutes, that anautomatic update of the
data of the device will run when the Auto Polling is active.
Auto COMTRADE Polling Interval (min):
interval, in minutes, that will be held the
automatic download of COMTRADE files.
Auto Polling COMTRADE Age (day):
maximum age, in days, of records that will be
downloaded automatically in Auto Polling. For example, if a register was made 5
days ago and the RPV Manager is started today and the Auto Polling COMTRADE Age
(day) is set to 4 (or 1, 2 or 3) the register will not be downloaded during the auto
polling.
Equipment Request Limit:
limit of records that will be requested from the equipment
in each query.
Retrieve Fault:
When selected, automatically downloads the short duration records,
both triggered and continuous.
Retrieve Disturbance:
When selected, performs the automatic download of the
slower disturbance records, both triggered and continuous.
Retrieve Travelling Wave (TW):
When selected, performs the automatic download of
the travelling wave records.
Retrieve Steady State (SS):
When selected, performs the automatic download of the
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...