Chapter 15
– Installation
RPV311
RPV311-TM-EN-7
219
The switch or circuit-breaker must be suitably located and easily reachable, also it
shall not interrupt the protective earth conductor.
Information about nominal voltage range, maximum voltage range, frequency and
power consumption, refer to Specifications Chapter 17: Technical Specifications.
7
RA331, RA332 and RA333 AC and DC Power Connection
show the wiring diagram for the AC and DC of the RA331, RA332 and
RA333 respectively.
Figure 107: AC/DC power connection
For compliance with IEC 61010, install a suitable external switch or circuit breaker in
each current-carrying conductor of RA33x power supply; this device should interrupt
both the hot (+/L) and neutral (-/N) power leads. An external 10 A, category C, bipolar
circuit-breaker is recommended. The circuit breaker should have an interruption
capacity of at least 25 kA and comply with IEC 60947-1 and IEC 60947-3. The switch
or circuit-breaker must be suitably located and easily reachable, also it shall not
interrupt the protective earth conductor.
For information about nominal voltage range, maximum voltage range, frequency
and power consumption, see Section 2.9 of the Specifications Chapter.
8
Powering Up
8.1.1
RPV311
Do not operate the unit without the safety ground connection in place;
Connect power cable (including safety grounding) to the unit;
A self-test will be executed and at the end, if no configuration has been sent, the
R
EADY
indicator on the front panel will light up;
If any pair of optical fibers has already been connected to the acquisition module, the
A
CT
indicator will light up, indicating that there is communication between the
modules;
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...