Chapter 15
– Installation
RPV311
RPV311-TM-EN-7
235
Place the board back in the case.
Secure the case by screwing the back panel and connecting the terminals cables.
Connections shall use insulated flexible wires of 1.5 mm² cross section, 8 mm ring
terminals, and M3 holes.
Before making the electrical connection, make sure the signal is applied in
accordance with the technical specifications of the equipment. For information about
DC transducer inputs specifications, see Chapter 17: Technical Specifications.
14.1.1
Connection diagram of the DC transducer inputs of ± 10 V
Figure 124: Connection Diagram of DC Transducer Inputs ± 10 V
15
Analog DC Transducer Inputs ± 20 mA
The RA331, RA332, and RA333 modules have up to 8, 16, or 8 analog inputs,
respectively, which can be configured for measurement of currents of DC
transducers of -20 mA to 20 mA. All channels are identified of 101 to 108 for the
RA331 and RA333, and 101 to 116 for the RA332.
Each analog input has three terminals: positive voltage, positive current and negative
terminal which are used for the current and for the voltage, as shown in
To define if the driver will measure current of a DC transducer it is necessary to select
an internal jumper in the module. The binary and analog inputs are galvanically
isolated.
Figure 125: Analog Input Terminals
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...