Chapter 17
– Technical Specifications
RPV311
RPV311-TM-EN-7
257
1.5
Optical IRIG-Input (optional)
Optical IRIG
Signal
IRIG-B004
Wavelength
820 nm
Fiber type
Multimode 62.5 / 125 µm
Connector
ST
Sensitivity
- 24 dBm
1.6
Dry-contact Relay Outputs
Dry-contact Relay Outputs
Max Voltage
250 Vdc
Max Current
1A
Load
Resistive
Contact Numbers
1 normally closed
3 normally open
Isolation Level
3.3 KVdc