To configure the links, access the S
AMPLED VALUES SUBSCRIPTIONS
section, shown in
Figure 14: Sampled Values subscriptions links configuration section
A
The E
NABLED
check box allows user to enable the Subscription link feature.
B
The S
AMPLED
VALUE
IDENTIFIER
text field allow user to insert the monitored Sampled
Values identification.
C
The MAC A
DDRESS
text field allow user to insert the monitored Merging Unit MAC
Address.
D
The APP ID text field allow user to insert the monitored Sampled Values APP ID.
E
The VLAN ID text field allow user to insert the VLAN ID of the monitored Sampled
Values.
F
The VLAN
PRIORITY
scroll box allow user to select the priority of the Sampled Values
data at the configured VLAN.
G
The S
AMPLE
R
ATE
scroll box allow user to select the Sampled Values sample rate. 80
points-per-cycle is used for protection purposes and 256 points-per-cycles is used for
measurement purposes.
H
The P
ACKET
L
OSS
T
OLERANCE
allow user to insert a package-loss rule.
In the Inputs section, shown in
it is possible to configure the analog inputs
of the Sampled Values configured in the previous section. It is important to configure
the analog inputs for voltage or current, according to the Sampled Values messages
received of the monitored Merging Unit.
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...