RPV311
Chapter 15
– Installation
RPV311-TM-EN-7
218
Figure 104: Pre-insulated tubular pin terminals
The pin terminals should be completely inserted into the header connector supplied
with the unit so that no metallic parts are exposed, as shown in Figure 105.
Figure 105: Header connector assembly
A safety ground lead shall be connected to the terminal marked with the protective
earth symbol.
For better electromagnetic compatibility, ground the unit using a 10 mm (0.4 in) wide
grounding strap to connect the back panel of the unit to a good grounding point on
the mounting rack.
6
RPV311 AC and DC Power Connection
show the wiring diagram for the AC and DC of the RPV311 respectively.
Figure 106: AC/DC power connection
For compliance with IEC 61010, install a suitable external switch or circuit breaker in
each current-carrying conductor of RPV311 power supply; this device should
interrupt both the hot (+/L) and neutral (-/N) power leads. An external 10 A, category
C, bipolar circuit-breaker is recommended. The circuit breaker should have an
interruption capacity of at least 25 kA and comply with IEC 60947-1 and IEC 60947-3.
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...