Model

 

SD200SA 

Description 

Generator Interlock Kit on BR 100 amp panel 

Main Breaker

 

200 Amp Horizontal throw 4 Handle Main Breaker 

Generator Breaker

 

Below Main 

 

          

 

WARNING 

Only qualified personnel should be working on the panel box 

An amateur should 

NEVER

 open the panel box 

Please follow all rules and regulations of the National Electric Code

 

 

Step 1:  Disassemble the interlock. Place the bottom plate (holes only) at edge of main breaker and this will line up with the bottom 

edge of the generator breaker and mark holes as in picture below. 

 

 
Step 2:  Turn off the main breaker and remove the panel cover.  
 
Step 3:  Drill holes as marked on panel cover with supplied 3/16 drill bit and remove all burs from drilling cover. 
 
Step 4:   Insert screws from rear of cover, install bottom plate, and install top plate (slotted) install thread lock to screws and install 

retaining nuts. Ensure proper movement. 

 
Step 5:  Install 2 pole Generator breaker below main breaker and place Generator Warning Sticker on Generator breaker. 
 