SecoGear 24kV-27kV Air Insulation Switchgear
28
Both the screws can be accessed only when the
earthing switch is in OPEN position
Attention: Don't fully remove the drive rod, otherwise all
the parts will fall out.
Attention: Replace the bevel gear assembly and
earthing switch in the same way. Use care to avoid
damage as the main body is much heavier.
•
Open the padlock on the operating hole of the earthing switch
•
Draw out the drive rod forward, then the parts of the drive rod
in the switchgear can be removed from backwards now.
•
Completely draw out the drive rod from another side at a
slight angle.
•
Loosen the 4 fixing screws on the fixing bracket (see figure
6/6), and then remove drive rod of the rear door interlock from
rear door, then draw out the drive rod backward.
•
Unscrew both of the bolts on the bevel gear (See figure 6/7).
Fixed screw of
the bevel gear
Flexible connection
of the earthing
switch and earthing
busbar
Figure 6/7: Fixing screw of bevel gear
Figure 6/8: Flexible cable between earthing Switch and earthing
busbar
•
Unscrew the flexible connections between the earthing switch and common earthing busbar (see figure 6/8)
•
Remove the fixing screw of the earthing switch, and then push the bevel gear and the main body of the earthing switch (See figure
6/9)
•
Now replacement can be done with the above instructions following the previous instructions in reverse order.
Remove 6 fixing
screw
s
o
f
the
earthing switch
Figure 6/9: Fixing screw of the earthing switch