User Manual
SG Series 225 & 300 UL S2
Code
Message
Meaning
4699
BATTERY TEST IMPOSSIBLE
Automatic Battery Test
is not possible due to:
−
No Utility Rectifier or Bypass.
−
Battery not fully charged.
−
Load is below 10% or above 80%.
Test is postponed for 1 week.
4763
REMOTE CONTROL ON
Inverter
can be started or shutdown by remote control.
Commands source can be chosen depending on the value
of parameter (Service only):
0 = Only
Local
Panel.
1 = Only
Remote
Control.
2 = Both.
4764
REMOTE CONTROL OFF
Inverter
cannot be started or shutdown by remote control.
Commands source can be chosen depending on the value
of parameter (Service only):
0 = Only
Local
Panel.
1 = Only
Remote
Control.
2 = Both.