Modifications reserved
Page 13/49
OPM_SGS_ISG_M75_M75_2US_V010.doc
Installation Guide
SG Series 750 UL S2
&
SG Series 750 T12 UL S2
3.1.1 Dimensions and weight
SGS_75
0_UPS d
imension
s_GE_01
Inverter ca
binet
Rectifier c
abinet
67"
1700mm
76.8
"
1950
mm
2020mm
79.5"
146.5"
3720mm
35.4"
900mm
Fig. 3.1.1-1 SG Series 750 & SG Series 750 T12 cabinet dimensions
SG Series 750
&
SG Series 750 T12
UPS dimensions
(W x D x H)
SG Series 750
&
SG Series 750 T12
146.5x35.4x76.8
inches (3720x900x1950 mm)
SG Series 750
&
SG Series 750 T12 - Inverter cabinet
79.5x35.4x76.8 inches (2020x900x1950 mm)
SG Series 750
&
SG Series 750 T12 - Rectifier cabinet
67x35.4x76.8 inches (1700x900x1950 mm)
Weights
SG Series 750
&
SG Series 750 T12
and options
Weight
(lbs./ Kg)
Floor Load
(lbs./sq ft / Kg/m
2
)
UPS rating with
Rectifier Configuration
Rectifier Inverter Rectifier Inverter
SG Series 750 (6 pulse) with 5
th
filter
3468 / 1573
6332 / 2872
211 / 1028
324 / 1580
SG Series 750 (6 pulse) with 5
th
& 11
th
filter
3607 / 1636
6332 / 2872
219 / 1069
324 / 1580
SG Series 750 T12 (12 pulse) without filter
5002 / 2269
6332 / 2872
304 / 1483
324 / 1580
SG Series 750 T12 (12 pulse) with 11
th
filter
5141 / 2332
6332 / 2872
312 / 1524
324 / 1580
NOTE !
The weight of each single piece is marked outside the package!