OPM_SGS_USM_10K_40K_0US_V010.doc
23/88
Operating
Manual
SG Series
10, 20, 30 & 40 kVA
6.1 METERING
MODE
The
metering mode
is entered any time the
metering
button is pressed.
While in this mode the LCD will display a series of screens containing metering information.
In this mode the buttons perform the following functions:
metering
Scrolls forward to the next screen.
alarms
Abandons
the
metering mode
and enters the
alarms mode
.
parameters
Abandons
the
metering mode
and enters the
parameters mode
.
+
Scrolls forward to the next screen.
–
Scrolls backward to the previous screen.
ok
Displays the main screen for this mode.
Main screen
This screen displays the current status of the UPS in a condensed form.
The information offered by this screen consists of:
•
The type of the machine: Family name, series number (P + unit number for parallel
version from 1 to 8) and power range.
•
The status of the load.
•
The
Load
amount as a percentage of the nominal
Load
(referred to the most loaded phase).
•
The estimated
Battery
backup time in minutes with the present load.
SG Series S0 30kVA
LOAD ON INVERTER
LOAD = 84%
Autonomie = 12min
metering
alarms
parameters
+
–
ok
Battery data screen
This screen displays:
•
The
Battery
voltage.
•
The
Battery Current
(negative values correspond to the discharge of the
Battery
).
•
The temperature of the
Battery
(XXX indicates sensor disabled).
•
The current charge level.
•
The estimated backup time with the present load.
Ub=540V Ib= + 15A
Battery Temp= + 20
°
C
Charge Level= 87%
Autonomy = 12min
metering
alarms
parameters
+
–
ok
Bypass Utility data screen
This screen refers to the AC source supplying the
Bypass
. This screen displays:
•
The frequency.
•
The voltage levels of the three phase voltages.
U TILIT Y
f = 60.0 H z
U 1=2 76V U 2=27 5V
U 3= 277V
m eterin g
alarm s
pa ram eters
+
–
ok