7.4.6 Parallel system shutdown (No Load supply)
The
Load
must be disconnected.
Initial status:
Load supplied from all Inverters
.
First operated unit
All other units of the system
1. Press
“
total off
”
button on any one on the units
.
•
Load
is disconnected from
UPS.
•
Rectifier
and
Inverter
are shut down and all output and input
contactors
will be
opened.
•
LED’s,
Rectifier, Inverter
and
Load
are OFF.
First operated unit
All other units of the system
2. Open Q1 (Pos. O) on all Units
.
First operated unit
All other units of the system