background image

4.1.3  Programmable input free contacts 

Some programmable UPS functions (indicated in 

Section 8.1

), can be activated by closing an external contact, if 

connected, on: 

 

X1 / 10, 21 

or

 

J2 / 10, 23 

User Input 1 (default = Not used) 

X1 / 11, 22 

or

 

J2 / 11, 24 

User Input 2 (default = Emergency GEN ON)

 

 

4.1.4  Gen Set Signaling (GEN ON) 

If an emergency generator set supplies the UPS in case of 

Mains Failure

 and the generator is considerably 

unstable in frequency, it should be suitable to install the signal 

Generator ON

 on 

X1 / 11, 22

 

or

 

J2 / 11, 24

). See 

Fig. 4.1-1 / X1 

and

 J2.

 

Since the Parameter for of the reading of the Generator function is password protected, call the nearest 

Service 

Center

 for it's activation. 

 

When this contact closes, it changes certain (programmable) functions such as: 

• 

Enabling or disabling of synchronization and consequently the 

Load

 transfer to generator. 

• 

Reduction or elimination or delay of 

Battery

 recharging during the generator operation. 

 

Additionally, when the 

Generator ON

 input contact is closed, the UPS will inhibit 

eBoost™ Operation Mode

 and 

revert to double-conversion operation. 

 

 

In a parallel system a separate NO (Normally Open) contact must be connected to each 
individual unit. 

 

4.1.5  AUX external Maintenance Bypass 

If the UPS system is equipped with an external 

Maintenance Bypass Switch

, it is possible to connect a 

NO

 (Normally 

Open) voltage-free aux. contact from the 

External Bypass Switch

 to the programmable input 

X1 / 10, 21

 or 

J2 / 10, 

23

, making the UPS operate as if the internal switch 

Q2 

has closed. 

This function can be activated by changing a dedicated parameter (password required). 

When this 

NO

 (Normally Open) contact closes, the output 

Inverter Contactor

 

K7

 it is automatically opened and the 

Load

 transfer back to 

Inverter

 will be inhibited. 

 

 

In a parallel system, the input on the customer interface of each unit must be connected to 
a separate AUX contact of the External Maintenance Bypass Switch. 

 

4.1.6  eBoost/IEMi control signal 

The UPS operation in either 

eBoost

 or 

IEMi

 operating modes can be controlled via an 

NO (Normally Open)

 contact by 

installing the “

eBoost/IEMi control

” signal, routed to the programmable function contacts (see 

Fig. 4.1-1 / X1

 and 

J2

). 

The Parameter for the activation of such function is password protected. Call the nearest 

Service Center

 for its 

activation. 

When this contact closes, 

eBoost

 or 

IEMi

 operation is inhibited. 

This function is particularly useful for controlling 

eBoost

 or 

IEMi

 operation following critical conditions on either the 

load side or the input utility, including generator operation when the “

Generator ON

” signal has not been installed. 

 

When using the “eBoost/IEMi control” function on the programmable user relays of the 
customer interface X1/J2 terminals in a parallel system, a separate NO (Normally Open) 
contact must be connected to each individual unit. 

 

 

4.1.7  Auxiliary Power Supply (APS) 24Vdc and Battery Breaker Release 

S

G

S

_40

0-5

0

0_

U

P

S

_X

A

-X

B

_01

1

XA

2

3

4

4

2

3

1

XB

 

Terminals XA 

 

1

2

3

4

SGS_400

-500_Ter

minals XA

_01

 

XA-1

 24Vdc 

XA-2

 GND 

 

XA-3

 Positive 

(+) 

Battery Breaker Release Voltage 

XA-4

 Negative 

(-) 

Battery Breaker Release Voltage

 

Fig. 4.1.7-1   Terminals XA for connection 24Vdc and Battery Breaker Release

 

Modifications reserved 

Page 39/41 

OPM_SGS_ISG_M40_M50_2US_V021.doc 

User Manual 

SG Series 400 & 500 UL S2

 

Summary of Contents for SG Series 400

Page 1: ...tallation Guide Uninterruptible Power supply SG Series 400 500 400 500 kVA 480Vac UL S2 GE Consumer Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 850 51 51 F 41...

Page 2: ...ined in this publication is intended solely for the purposes indicated The present publication and any other documentation supplied with the UPS system is not to be reproduced either in part or in its...

Page 3: ...erform start up and commissioning of the UPS Please Contact GE GLOBAL SERVICES at least two weeks prior to schedule start up and commissioning at 1 800 637 1738 or by E mail at pqservice ge com Distri...

Page 4: ...00 is a product that needs to be installed by a licensed and knowledgeable contractor We recommend that this manual be kept next to the UPS for future references If any problems are encountered with t...

Page 5: ...nd External Battery Breaker connection 29 3 8 5 Interface to External Bypass for single unit 30 3 8 6 Connections to External Bypass switch in case of RPA Parallel System 30 3 8 7 Set up for SG Series...

Page 6: ...removing the sidewalls of the UPS make sure that all earth connections when reassembling are correctly reattached This UPS is intended for use in a controlled indoor environment free of conductive co...

Page 7: ...attery terminals Do not allow a tool to short between individual or separate battery terminals or to the cabinet or rack Do not lay tools or metal parts on top of the battery and do not lay them where...

Page 8: ...may occur CAUTION internal parts have dangerous voltage present Risk of electric shock PE Earth GND Ground PROTECTIVE GROUNDING TERMINAL A terminal which must be connected to earth ground prior to mak...

Page 9: ...0 general view with optional 5th harmonic filter and removed protection panels 1 Opening for top cable entry 2 Opening for bottom cable entry 3 Bus bars for Utility input and Load output 4 Bus bars fo...

Page 10: ...e of the center of gravity marked on the package Take all necessary precautions to avoid damage to the cabinet while hoisting the UPS NOTE Check for sufficient floor and elevator loading capacity Fig...

Page 11: ...3 3 2 Some important functions of the UPS such as the customized functions are defined by parameters stored in a RAM memory A small backup battery located on the Control Unit board supplies the RAM I...

Page 12: ...I filtering is inherent to the UPS there is no guarantee that the UPS will not influence sensitive devices such as cameras and monitors that are positioned close by If interference is expected the UPS...

Page 13: ...47 80mm 3 15 2 050mm 80 71 30mm SGSU_400 500_S2_UPS view bottom_01US Please remove the plate before drilling any holes Fig 3 4 1 3 Opening on the bottom of the cabinet for input and output cables Fix...

Page 14: ...timal room temperature for Battery storage is 68 F 20 C to 77 F 25 C and shall never exceed the range 4 F 20 C to 104 F 40 C The life of valve regulated batteries will be reduced by 50 for each additi...

Page 15: ...Dealer or the nearest Service Center for appropriate solutions In order to prevent overheating of the UPS the available air intake flow rate must exceed the total air exhaust flow rate requirement of...

Page 16: ...ndicator for shock and TiltWatch indicator for overthrow on the outside These devices indicate an eventual shock or overthrow during transport Whenever these devices show a possible anomaly the UPS sh...

Page 17: ...and are indicated with an appropriate symbol on the assembly layout drawing see Fig 3 6 1 For parallel systems the delivery also includes the bus control cables for inter connecting the UPS modules Pa...

Page 18: ...Fuses are opened there is a supply failure to the Rectifier as well as to the Bypass and Manual Bypass In this case the interconnection links BR1 BR2 and BR3 on the input terminals or bus bars MUST R...

Page 19: ...ing four pole circuit breakers as protection A potential problem exists for situations with non linear loads The neutral current could be greater than the phase currents The three phase Utility power...

Page 20: ...put Rectifier AC Input Bypass AC Input DC Input F1 F3 UPS rating Max F2 Nom Nom Max F4 SG Series 400 512 A 615 A 481 A 512 A 615 A 702 A SG Series 500 617 A 708 A 600 A 617 A 708 A 960 A Size of Branc...

Page 21: ...150 170 100 120 135 2 0 145 175 195 115 135 150 3 0 165 200 225 130 155 175 4 0 195 230 260 150 180 205 250 215 255 290 170 205 230 300 240 285 320 190 230 255 350 260 310 350 210 250 280 400 280 335...

Page 22: ...eld wiring connections can be made from the front side by removing the front right side panel protection cover panel E as indicated in Fig 3 8 1 1 be advised that installation performed from the front...

Page 23: ...move the plate before drilling any holes Detail of the power wiring terminal for the AC input output Detail of the power wiring terminal for external battery connection 2 51mm 0 57 14 5mm 2 51mm 2 51m...

Page 24: ...INPUT OUTPUT power wiring Bus Bars Cable terminations are to the Rectifier Input Output Bus Bars as shown above Connect wire to the Bus Bars using appropriate tools and appropriate torque Torque spec...

Page 25: ...the Bypass Input 3 wire input ground and the Load does not require a Neutral solidly connect the Output Neutral of the UPS to ground in the Output Distribution Cabinet Wire Neutral Conductors from the...

Page 26: ...Bus Bars as shown above Connect wire to the Bus Bars using appropriate tools and appropriate torque Torque specification for two hole lugs on Bus Bars see Section 3 8 1 Dual Input Configuration Recti...

Page 27: ...the Bypass Input 3 wire input ground and the Load does not require a Neutral solidly connect the Output Neutral of the UPS to ground in the Output Distribution Cabinet Wire Neutral Conductors from the...

Page 28: ...BR2 and BR3 MUST BE REMOVED in case of dual input utility Fig 3 8 3 3 AC bus bars BR1 BR2 and BR3 For separate Bypass and Rectifier input configuration option the AC Bus Bars BR1 BR2 and BR3 MUST BE R...

Page 29: ...connection between the UPS and external Battery must be done by using a shielded cable or suitable shielded steel conduit External Battery Breaker Release Fig 3 8 4 2 External battery breaker connecti...

Page 30: ...External Bypass for single unit SG Series 400 500 has to be interfaced to the External Bypass Auxiliary Contacts NO for safety reasons This will prevent contactor K7 from closing when the external byp...

Page 31: ...e Center for more information NOTE If an emergency generator set supplies the UPS in case of Mains Failure and the system is intended to be operated in eBoost Operation Mode eBoost operation shall be...

Page 32: ...Center which will help you find cost effective solutions The AC input power of the Bypass must be the same for all units of the parallel system no phase shift allowed between units NOTE It is strongly...

Page 33: ...of the control bus cable between two parallel unit is 40 ft 12 m Maximal overall length of bus connection between the first and the last unit should not be longer than 276 ft 84 m Verify that control...

Page 34: ...2_RPA IM0048_03 JA2 JB2 JP2 JP1 Fig 3 9 2 3 Bus connection on intermediate units Intermediate units On the parallel bus PCB P34 Bus Interface of the intermediate units of the parallel system the Jumpe...

Page 35: ...nits must be made on the electronic module P34 Bus Interface situated at the inside of the UPS door Next parallel unit JA SGSU_400 500_S2_RPA control bus cable_02US A JA1 JA2 JB B JA1 JA2 Fig 3 9 3 2...

Page 36: ...s JA and JB inside the UPS cabinet In case one unit should be removed from the parallel system the bus cables JA and JB must be removed from the cabinet without disconnecting them from the metal plate...

Page 37: ...O def RL2 1 12 13 2 14 3 15 4 16 5 17 6 18 7 19 8 20 9 21 10 22 11 1 14 9 1 X1 J2 J3 J5 J4 2 1 JP3 Fig 4 1 1 Customer interface NO Normally Open C Common NC Normally Closed The connectors J4 and J5 ca...

Page 38: ...minal blocks X1 The meaning of the alarms on the free contacts in standard configuration default is the following X1 1 2 3 or J2 1 2 3 NO C NC Utility Failure X1 4 5 6 or J2 4 5 6 NO C NC Load on Inve...

Page 39: ...ted by changing a dedicated parameter password required When this NO Normally Open contact closes the output Inverter Contactor K7 it is automatically opened and the Load transfer back to Inverter wil...

Page 40: ...als XB_01 4 2 3 1 Fig 4 1 8 1 Terminals XB for connection EPO SGS_400 500_Customer interface EPO_01 JP3 J2 Fig 4 1 8 2 Customer interface NOTE This procedure could imply a Load shut down NOTE In case...

Page 41: ...otes with date and short description all the operations performed on the UPS as maintenance components replacement abnormal situations etc Date Description Done by Modifications reserved Page 41 41 OP...

Reviews: