Critical Power
Modifications reserved
Page 41/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide
SG Series 10-20-30-40 UL S
4
CUSTOMER INTERFACE
4.1
CUSTOMER INTERFACE
Fig. 4.1-1 Customer interface
Serial port J3 - RS 232 (sub D - female 9 pin) (see
Section 4.1.1)
Suitable for JUMP protocol
Pin 2
: TX (out)
Pin 3
: RX (in)
Pin 5
: GND
J2 (subD-female 25p) – Output signals on voltage free contacts(see
Section 4.1.2)
J2
/
1, 2, 3
NO, C, NC
Utility Failure
(default Parameter RL=1)
J2/4, 5, 6
NO, C, NC
Load on Inverter (default Parameter RL=3)
J2/7, 8, 9
NO, C, NC
Stop Operation
(default Parameter RL=5)
J2/14, 15, 16
NO, C, NC
Load on Utility
(default Parameter RL=2)
J2/17, 18, 19
NO, C, NC
General Alarm
(default Parameter RL=4)
J2/20, 21, 22
NO, C, NC
Acoustic Alarm
(default Parameter RL=6)
Signals on terminals
X1
and on connector
J2
are in parallel and
therefore not separated galvanically from each other.
The programmable signals on
X1
and
J2
will be disabled with
Q1
open, with the
exception of the signals for
“16 - Manual Bypass ON”
and
“26 - EPO”
.
XB - Terminals for
EPO
connection(see
Section 4.1.7)
XB/1, 4
or
J2/12, 25
NC
EPO
(Emergency Power Off)
Note: to enable this function, remove cable short-circuiting XB / 2 – 3 and the
Jumper JP3 on P4 – Customer Interface
.
X1 – Output signals on voltage free contacts – terminals (see
Section 4.1.2)
X1/1, 2, 3
NO, C, NC
Utility Failure
(default Parameter RL=1)
X1/4, 5, 6
NO, C, NC
Load on Inverter (default Parameter RL=3)
X1/7, 8, 9
NO, C, NC
Stop Operation
(default Parameter RL=5)
X1/12, 13, 14
NO, C, NC
Load on Utility
(default Parameter RL=2)
X1/15, 16, 17
NO, C, NC
General Alarm
(default Parameter RL=4)
X1/18, 19, 20
NO, C, NC
Acoustic Alarm
(default Parameter RL=6)
Input contacts (see
Section 4.1.3)
X1/10, 21
or
J2/10, 23
Programmable (default = RL1)
X1/11, 22
or
J2/11, 24
Programmable / Generator ON (NO) (def. = RL2)
NO
= Normally Open
C
= Common
NC
= Normally Closed
The connectors
J4
and
J5
can be used for additional
3-ph SNMP/WEB plug-in adapter
or an additional
Customer
Interface
(installation only when the UPS is switched Off).
XA
: terminals for 24Vdc Auxiliary Power Supply connection.
XB
: terminals for
EPO
connection.
Programmable user relays
Programmable functions on contacts (X1 - J2)
On terminals
X1
or
J2
connector, six of the following
26
signals
can be selected from the display, entering with
the appropriate password.
Some UPS functions can be activated with
parameters when an external Normally Open
contact is closed on:
X1-10, 21 / J2-10, 23
or
X1-11, 22 / J2- 11, 24
Selectable functions by changing
parameters
(password required) are:
0 - No function
1 - Inverter ON
2 - Inverter OFF
3 - Print All
4 - Status Relay
5 - Generator ON
6 - External Bypass ON
7 - External Battery Fuses, or External K3
See Alarm 4104 - “Battery Fuses”
Voltage free contacts:
Max. DC / AC: 24V / 1.25A
IEC 60950 (SELV circuit)
Min. Signal Level: 5Vdc/5mA
0- No Information
1- Buzzer
2- General Alarm
3- Load on Utility
4- Stop Operation
5- Load on Inverter
6- Utility Failure
7- DC Over Voltage
8- Low Battery
9- Overload
10- Over Temperature
11- Inverter-Utility not syncr.
12- Bypass Locked
13- Bypass Utility Failure
14- Rectifier Utility Failure
15- Battery Discharge
16- Manual Bypass ON
17- Rectifier ON
18- Inverter ON
19- Boost Charge
20- Battery Earth Fault
21- Battery Fault
22- Relay Input 1
23- Relay Input 2
24- Relay Output ON
25- Relay Output OFF
26-
EPO
(Emergency Power Off)
1
12
13
2
14
3
15
4
16
5
17
6
18
7
19
8
20
9
21
10
22
11
1
14
9
1
X1
J2
J3
SGSU_100-150_Customer interface_01
J5
J4
XA
2
1
XB
1
2
3
4
1
2
3
4
JP3