background image

GEH-62840 

Power Break®  II  Circuit Breaker 

Accessories 

Shunt  Trip and Shunt  Trip  with Lockout 

Introduction 

The  Shunt  Trip  and  Shunt  Trip  with  Lockout 
accessories,  shown  in  Figures  1  and  2,  can  be  installed 
in  800-4000  ampere  frame  Power  Break®  II  circuit 
breakers.  These  accessories  allow  the  breaker  to  be 
tripped  electrically  from  a  remote  location. 
In  addition  to  providing  a  trip  signal  to  the  breaker, 

the Shunt  Trip accessories  can be set up  to  interact  with 

other  Power  Break  II  accessories,  when  used  with  a 

MicroVersaTrip  Plusn1  or  MicroVersaTrip  PMn1  Trip 

Unit.  DIP  switches  on  the  rear  of  the  breaker  Trip 
Unit  can  configure  the  Shunt  Trip  accessories  to 
activate  a  Bell  Alarm-Alarm  Only  accessory  or  a  Bell 

Alarm  with  Lockout  accessory  when  a  shunt  trip 

occurs.  The  Accessory  Configuration  section  below 
describes  how  this  can  be  done.  If  the  breaker  i s  
equipped  with  a  Power+n1  Trip  Unit,  it  is  configured 
so  that  only  protection  trips  will  activate  a  Bell  Alarm­

Alarm  Only  or  Bell  Alarm  with  Lockout. 

Figure 

1. 

Shunt Trip. 

Figure 

Shunt Trip with Lockout. 

The  catalog  numbers  for  various  voltage  applications 
are  listed  in  Table  1  for  the  Shunt  Trip  and  in  Table 2 
for  the  Shunt  Trip  with  Lockout. 

Catalog 

Voltage 

Peak  Inrush 

Nominal  RMS 

Number 

Rating 

CD 

Current,  A@ 

Current,  mA 

SPST012 

12 

Vdc 

3.0 

200 

SPST024 

24 

Vac 

1.5 

140 

24 

Vdc 

SPST048 

48 

Vac 

1.5 

110 

48 

Vdc 

SPST120 

120 

Vac 

1.5 

85 

125 

Vdc 

SPST208 

208 

Vac 

1.5 

50 

SPST240 

240 

Vac 

1.5 

40 

250 

Vdc 

CD  24-240 

Vac  devices  are rated for 

50/60  Hz. 

<2l 

Peak inrush current is  present  for 

2-6 

ms  after  activation.  This 

number is provided  so that fuses and supplies can  be chosen 
appropriately. 

Table 

1. 

Catalog numbers and voltages for the Shunt Trip. 

Catalog 

Voltage 

Peak  Inrush 

Nominal  RMS 

Number 

Rating 

CD 

Current,  A 

<2l 

Current,  mA 

SPSTL012 

12 

Vdc 

19 

300 

SPSTL024 

24 

Vac 

15 

300 

24 

Vdc 

SPSTL048 

48 

Vac 

7.5 

200 

48 

Vdc 

SPSTL120 

120 

Vac 

3.0 

80 

125 

Vdc 

SPSTL208 

208 

Vac 

1.9 

60 

SPSTL240 

240 

Vac 

1.5 

45 

250 

Vdc 

Table 

Catalog  numbers and voltages for the Shunt  Trip with Lockout. 

Operation 

Apply  control  voltage  to  terminals  31  and  32  of  the 

terminal  strip  on  the  right  side  of the  breaker  to  trip 

the  circuit  breaker.  The  Shunt  Trip  will  cause  the 

circuit  breaker  to  trip  when  the  control  voltage  i s  
greater  than  75%  o f  the  rated  de  voltage  or  55%  of  the 
rated  ac  voltage.  Control  power  to  the  Shunt Trip must 

be  removed  before  the  breaker  can  be  closed.  Control 
power to  the  Shunt  Trip  with  Lockout  must  be  removed 
for a  minimum  of  0.25  second  before  the  breaker  can 
be closed. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for Shunt Trip

Page 1: ... Trip with Lockout Catalog Voltage Peak Inrush Nominal RMS Number Rating CD Current A Current mA SPST012 12 Vdc 3 0 200 SPST024 24 Vac 1 5 140 24 Vdc SPST048 48 Vac 1 5 110 48 Vdc SPST120 120 Vac 1 5 85 125 Vdc SPST208 208 Vac 1 5 50 SPST240 240 Vac 1 5 40 250 Vdc CD 24 240 Vac devices are rated for 50 60 Hz 2l Peak inrush current is present for 2 6 ms after activation This number is provided so t...

Page 2: ...ipped with a MicroVersaTrip Plus or MicroVersaTrip PM Trip Unit the Shunt Trip accessory can be configured to activate installed Bell Alarm Alarm Only or Bell Alarm with Lockout accessories when a shunt trip occurs with the procedure described in the Accessory Configuration section 6 Connect the control wiring for either Shunt Trip to terminals 31 and 32 at the terminal block on the right side of ...

Page 3: ...breaker cover Remove the cover from the breaker face 3 Pull the Trip Unit locking lever to the right then hold the Trip Unit near the battery cover and li t it straight out of the breaker 4 Refer to Figure 5 and Table 3 to det rmine the switches to be changed 5 Push in the appropriate Enable or Disable side of the switch 6 Confirm all switch settings before remstaiiing the Trip Unit in the breaker...

Page 4: ...eck that the Trip Unit is seated correctly If the Trip Unit was removed to set the switches check that it has been correctly installed remove and reinstall if necessary Note that an otherwise unpowered Trip Unit is powered up by an energized Shunt Trip Verify that the breaker is closed Check that the Shunt Trip with Lockout control power is applied at greater than 75 of the rated de voltage or 55 ...

Reviews: