background image

8

 

Simon® XTi Installation Guide

 

Mounting Recommendations: 

• 

Where possible, install sensors within 100 feet (30 m) of 

the receiver. While a transmitter and receiver combination 

may have an open-air range of 500 feet (152 m) or more, 

the environment at the installation site may have a 

significant effect on operational range. Changing a sensor 

or receiver location can improve wireless communication.  

• 

Avoid mounting sensors or receivers in areas where they 

will be exposed to moisture or where the operating 

temperature range will exceed the specified range (10 to 

120 °F).  

• 

Avoid mounting the sensor or receiver in areas with a 

large quantity of metal or electrical wiring. For example: 

within 1 meter of AC distribution panel (fuse box), HVAC 

duct work.  

• 

Avoid mounting the sensor or receiver directly on metal.  

• 

The Simon® XTi system should not be mounted within 3 

meters of any other RF equipment (RF music system 

transmitter, wireless router/modem, etc.).  

Note: 

Refer to specific sensor installation instructions for 

complete operation and testing details. 

Table 6: Device programming 

 

Device 

To program 

Door/window 
sensor 

Press the button on the top of the sensor (cover 
removed) or trip the tamper. 

Motion sensor 

Press the button on the back of the sensor 
(mounting plate removed) or trip the tamper. 

Smoke detector 

Trip the tamper, press the test button, remove the 
detector from its base, or put the smoke detector 
into alarm. 

Hardwired 
sensor 

Separate the sensor from its magnet. 

CO alarm 

Trip the wall tamper by removing the sensor body 
from the mounting plate. 

Simon XT 
talking touch 
screen 

1. Press the Settings icon. 
2. Press the Down arrow until the Clear and Enroll 
icon appears. 
3. Press the Clear and Enroll icon. The touch 
screen should indicate it is waiting for enrollment.  

Simon XT 
talking  
touchpad 

Press the Lights off button on the touchpad six 
times in rapid succession. On the sixth press, the 
touchpad makes a longer beep. 

Key fob 

Press the lock and unlock buttons at the same time. 

To learn (program) a sensor: 

1.  From the Programming screen, enter the access code 

from the codes listed in Table 5 on page 7. The display 

shows each entered access code digit as a dot. 

2.  Press OK. You are now in the programming screen. 

3.  Press Sensors.  

4.  Press Learn Sensor. 

5.  Trip the sensor (see Table 6 above). The Edit Sensor 

screen will appear. If no further action is required (change 

sensor name, number, or group) proceed to step 8.  To 

exit, press Close repeatedly. 

6.  To change the sensor name, number, or sensor group 

press the appropriate Edit icon and modify the value.  To 

change the sensor text, press the appropriate Edit icon, 

then choose the item you would like to change. 

7.  Press Save to keep the new sensor, or Cancel to abort 

learning this sensor into the system (both of these choices 

will return you to step 5). 

8.  To exit, press Close repeatedly. 

Sensor Naming 

Please use the following guide when naming sensors: 

• 

Sensor names must have the word “window” or “door” 
from the text library to interact with the touch screen Door 

and Windows icons on the Main screen. 

• 

On the Edit Sensor name screen in programming, default 

the screen to list and not keypad. This gives the user the 

list of possible sensor names. 

• 

The Motion icon is controlled by sensors that are 

programmed into the following groups: 15, 17, 18, 20, 28, 

or 32. 

• 

The Property icon is controlled by the following sensors: 

• 

All sensors learned into Group 43. 

• 

Sensors that are not named “window” or “door”. 

• 

Sensors not learned into the Motion groups. 

• 

Sensors that are named keyfob, keychain or 

touchpad. 

Sensor Testing 

Test the sensors after all programming is completed and 

whenever a sensor-related problem occurs. 

Note: 

While the sensor test is a valuable installation and 

service tool, it only tests sensor operation for the current 

conditions. You should perform a sensor test after any change 

in environment, equipment, or programming. 

Notify the central station you will be performing a test prior to 

starting the test.  

To test the sensors: 

1.  Place all sensors in their secured (non alarm) state. 

Summary of Contents for Simon XTi

Page 1: ...24 RF TS d 00 01 04 05 06 or 07 Simon XT Talking Touchpad 60 924 3 XT b 01 Carbon Monoxide alarm TX 6310 01 1 b 600 6520 95 b 34 a Not certified as a primary protection circuit for UL listed systems and is for supplementary use only b Has not been investigated by UL c Required for UL listed residential fire alarm applications d The TWTTS has been verified for use by ETL Neither this device nor oth...

Page 2: ...ote Mark both mounting holes in the middle of the mounting slot This will allow better adjustment of the panel before securing it to the wall Figure 2 Mounting holes 7 Secure the mounting screws provided to the locations on the wall marked in step 6 Do not tighten the screws Leave enough clearance to mount the mounting plate Note Use wall anchors if no studs are present 8 Mount the mounting plate ...

Page 3: ... kohm resistor as shown in Figure 4 below The resistor must be connected at the last switch in the circuit Figure 4 Normally closed hardwired reed switches Note Do not install the resistor at the panel terminals This does not provide supervision of the wire Wiring phone lines You can connect a phone line to the panel for systems monitored by a central monitoring station or systems that notify user...

Page 4: ...latch back to remove the battery 4 Insert the new battery into the battery compartment and snap into place 5 Plug the battery connector into the panel CAUTION Do not connect the battery until you are ready to power up the panel ATTENTION Ne branchez pas la batterie tant que vous n êtes pas prêt à mettre le panneau sous tension Resetting memory to factory defaults If you need to reset memory to fac...

Page 5: ...m Messages will also display on this icon describing what caused the alarm Press this icon to cancel the alarm Item Description These four icons depict the status of the sensors installed in your system A green check indicates sensors are closed or no recent activity detected A red exclamation indicates sensors are open or recent activity has been detected Pressing these icons will open a new scre...

Page 6: ...ty Otherwise the default will be the Home screen and the screen will always be lit If AC power is lost the screen will go blank after 2 minutes of inactivity to maximize battery life Note The screen will automatically go blank at 2 00 am daily for 60 minutes Calibration Press the Show icon to enter the calibration screen This screen will allow you to recalibrate the touch screen Help Press the Hel...

Page 7: ...21 This code is limited to changing all but the following Dealer code code length downloader code phone lock phone 1 phone 2 phone 1 report mode phone 2 report mode HW1 function Access codes Table 5 below describes the Access code menu programming options Table 5 Access codes Function Default Description Dealer code 4321 You can use the dealer code to program all system options including high secu...

Page 8: ...longer beep Key fob Press the lock and unlock buttons at the same time To learn program a sensor 1 From the Programming screen enter the access code from the codes listed in Table 5 on page 7 The display shows each entered access code digit as a dot 2 Press OK You are now in the programming screen 3 Press Sensors 4 Press Learn Sensor 5 Trip the sensor see Table 6 above The Edit Sensor screen will ...

Page 9: ...nsor testing a 1 1 or greater touch screen press the Settings gear icon scroll down and then press the RF Test icon 6 of 8 6 Press Close repeatedly to exit Sensor Test Failure If sirens do not beep when a sensor is tripped use an RF Sniffer 60 401 test tool to verify that the sensor is transmitting Constant beeps from the RF Sniffer indicate a faulty sensor Replace the sensor If possible locate se...

Page 10: ...ition a trouble signal will be annunciated indicating that the battery may no longer support a full alarm load When fully charged the battery will operate the panel without AC power for 24 hours with the panel in a normal standby condition followed by 5 minutes in full alarm condition including the maximum specified auxiliary load of 250 mA Radio frequency 319 5 MHz Storage temperature 29 to 140ºF...

Page 11: ...ed Communication test Enabled Enabled Exit extension On On Swinger shutdown On one trip On one trip Function Default setting Required setting Fire alarm verify Off On Duress panic code Disabled Disabled Cross zone Disabled Disabled for zones with high probability of false alarms Table 9 below describes nonprogrammable hard coded system operation as required to meet ANSI SIA CP 01 Table 9 Nonprogra...

Page 12: ...cations Changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment FCC Part 15 registration number B4Z 910C SIMON IC 1175C 910CSIMO This Class B digital apparatus complies with Canadian ICES 001 Cet appareil numérique de la classe B est conforme à la norme NMB 003 du Canada Part 68 This equipment complies with Pa...

Reviews: