Figure 6. Securing the module to the interior.
Figure 6. Fixation du module à l’intérieur.
4. Wire the circuits.
Refer to the label on the circuit
breaker for the proper tightening torque.
5. Install lug covers on line and load ends of breaker.
Secure with plastic threads cutting screws provided in
kit.
6. Filler plate kits.
Install filler plate kit AFP4FGSB on
the module for breakers used as a branch.
AFP4FGSM for breakers used as a main.
Procedure for Aluminum
Terminations
1.
Strip the insulation, being careful to not nick the
wire.
2.
Clean the wire strands with a wire brush.
3.
Thoroughly coat the stripped conductor with a
suitable antioxidant compound, such as ALNOX or
PENETROX A13.
4.
Insert the conductor and tighten the connector screw
to the torque indicated on the rating label.
6. Kits de plaque d’obturation.
Installer le kit de plaque
d’obturation AFP4FGSB sur le module pour un
disjoncteur utilisé comme dérivation. Installer le kit
AFP4FGSM pour un disjoncteur utilisé comme
principal.
Procédure pour les raccordements en
aluminium.
1.
Dénuder l’isolation, en prenant soin de ne pas
entailler le câble.
2.
Nettoyer les brins du conducteur avec une brosse
métallique.
3.
Bien enduire le conducteur dénudé d’une pâte anti-
oxydante convenable telle que ALNOX ou
PENETROX A 13.
4.
Insérer le conducteur et serrer la vis du connecteur
au couple indiqué sur l’étiquette de calibrage.