background image

For  double-branch  devices,  repeat  this  procedure  for
the  second  breaker.  Combinations  of  circuit  breaker
types  TEB,  TED,  THED,  SEDA,  SEHA,  SELA,  or
SEPA  may  be  used.  Breaker  type  TEL  may  be  used
only with a breaker of like type.

Figure 4. Installing the breaker on the module.

4. Position  the  breaker  module.

  Loosen  the  latch  lock

screws and fully retract the latches, as shown in Figure
5.  Line  up  the  guide  fingers  on  both  ends  of  the
module  with  the  notches  in  the  panelboard interior
rails. Allow no space between units.

Figure 5. Positioning the breaker module.

5. Install  the  module.

  Latch  one  side  of  the  circuit

breaker  module.  Release  the  rail  latch.  Pivot  the
module  onto  the  bus  bars  and  engage  the  second
latch.  Release  the  rail  latch.  Tighten  the  rail  latch
screws to 25 in-lb, as shown in Figure 6.

Figure 6. Installing the breaker module.

6. Wire  the  circuits. 

Refer  to  the  label  on  the  circuit

breaker for the proper tightening torque.

7. Filler plate kits.

 Install the appropriate filler plate kits,

as listed in Table 1.

Filler Plate

Cat. No.

Module Type

AFP3SED

AMC6EB
AMC4SE

AFP2TED

AMC4EB

AFP4SED

AMC6EBS
AMC4EBS

AFP3ELD

AMC6EL

Table 1. Filler plate kit for each breaker module type.

Attention – Procedure for Aluminum
Terminations

1.

Strip the insulation, being careful to not nick the wire.

2.

Clean the wire strands with a wire brush.

3.

Thoroughly  coat  the  stripped  conductor  with  a
suitable  antioxidant  compound,  such  as  ALNOX  or
PENETROX A13.

4.

Insert the conductor and tighten the connector screw
to  the  indicated  torque,  as  indicated  on  the  rating
label.

Lug

Cover

Stud

Post

#10-32 Screw-

Washer

Assembly

#8-32 Screw &

Cup Washer

Filler

Support

Latch

Screw

Latch

Latch

Screw

Latch

Latch

Screw

Reviews: