9.
Install the center filler and terminal cover.
Install the
center filler [2] over the center of the assembly, as shown
in Figure 25. Secure the cover with thread-cutting screws
[15]. Tighten the screws to 6.5 in-lb. To install the
terminal cover toward the load or OFF side of the circuit
breaker, see instruction sheet DEH40404 (Lug Kits for
FG Breakers).
10. Insulate unused strap surfaces.
The double-branch
assembly may be installed with only one active circuit
breaker and the other branch left open for future use. In
this case, insulate the exposed surfaces of the strap
contact blocks in the unused branch. Cover the contact
surfaces with two layers of a UL-recognized 105° C
thermoplastic tape (OANZ2, such as Permacel P-30-105
or 3M 66R) to achieve a minimum insulation thickness of
0.013 inch.
Figure 25. Installing the terminal cover over the breaker
terminals.
Figure 25. Installation du couvercle de terminal par-dessus les
terminaux de disjoncteur.
10. Isoler les surfaces inutilisées des brides
. L’assemblage
double dérivation peut être installé avec un seul
disjoncteur actif et l’autre dérivation laissée ouverte pour
future utilisation. En ce cas, isoler les surfaces exposées
des blocs de contact des brides dans la dérivation
inutilisée. Couvrir les surfaces de contact avec deux
couches de ruban thermoplastique reconnu UL- 105° C
(OANZ2, tel que Permacel P-30-105 ou 3M 66R) afin
d’obtenir une épaisseur minimale d’isolation de 0.013
pouce.
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be
met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems
arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE Company.
g
GE Consumer & Industrial
General Electric Company
41 Woodford Ave., Plainville, CT 06062
DEH41047 R02 1206
© 2006 General Electric Company
Ces instructions n’ont pas pour propos de couvrir tous les détails ou variations de l’équipement ni de fournir des solutions pour tous les
imprévus reliés avec les opérations causées par l’installation ou l’entretien. Si des informations supplémentaires étaient requises ou s’il
survenait un problème lesquels ne sont pas suffisamment couverts selon l’acheteur, ceci devrait être référé à GE Company.