background image

6. 

Remove  the  Motor  Operator  Mechanism,  if 
present,  following  the  reverse  of the  installation 
procedure  described  in 

GEH-6281. 

7. 

While  holding  the  charge  interlock  rod  of  the 
breaker  down  against  the  midcover,  move  the 
Remote  Close  under  the  spring  frame  until  it 
rests  against  the  side  frame  of  the  breaker 
mechanism,  as  illustrated  in  Figure 

3. 

Slide  the 

Remote  Close  under  the  breaker's  torque 

tube 

until  the  Remote  Close  engages  the  closing  lever 
projecting  through  the  breaker  side  frame. 

8. 

Align  the  two  captive  Philips-head  mounting 

screws  with  the  threaded  holes  in  the  mecha­
nism  side  frame.  Tighten  to 

32 

in-lb. 

9. 

Attach  the  wire  connector  to  the  mating  color­
coded  (brown  and  yellow)  wires,  as  shown  i n  

Figure 

4. 

The  mating  wires  are  secured  to  the 

breaker  frame  at  the  factory  with  a  wire  tie.  The 
wire  tie  may  have  to  be  remoYed  to  allow  the 

wires  to  connect. 

10. 

Route  and  tie  the  wires  as  shown  in  Figure 

4. 

Use  two  ties  and  ensure  that  the  wires  do  not 

interfere  with  any  moving  parts  in 

the 

mechanism.  Check  that  the  wires  are  not  in  a 
position  to  be  pinched  by  or  interfere  with  the 
reinstallation  of  the  breaker  top  cover 

ll. 

Reinstall  the  Motor  Operator  Mechanism,  if 
present. 

12. 

Reinstall  the  secondary  terminal  block  onto  the 
breaker  midcover  terminal  block  mounting 
ridge  and  fasten  with  the  screw  previously 
removed. 

13. 

Test  the  Remote  Close  electrically  according 

to 

Table 

1. 

14. 

Reinstall  the  breaker  top  cover  and  tighten  the 
four 

#10-32 

screws  to 

15 

in-lb. 

15. 

Replace  the  trim  plate  and  tighten  the  four 

#8-32 

screws  to 

20 

in-lb. 

16.  Affix 

the  accessory  rating  label  to  the  side  of  the 

breaker. 

Affix 

the  ELECTRICALLY  OPERATED 

label  to  the top cover  above the  ON-OFF  indicator. 

Figure 

Removal of the breaker top cover. 

Figure 

3. 

Installation of the Remote Close under the breaker spnng 

frame. 

Figure 

4. 

Routing of the Remote Close wiring and the locations of the 

wire ties. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for SPRCS024

Page 1: ...mement Use the following procedure to install the Remote Close accessory into the circuit breaker 1 Verify that the rating on the Remote Close identification plate matches the electrical data required for the application as listed in Table 1 2 Tum the breaker off and discharge the closing spring by depressing the OFF and ON buttons in the sequence OFF ON OFF Verify that the breaker OFF ON indicato...

Page 2: ... Route and tie the wires as shown in Figure 4 Use two ties and ensure that the wires do not interfere with any moving parts in the mechanism Check that the wires are not in a position to be pinched by or interfere with the reinstallation of the breaker top cover ll Reinstall the Motor Operator Mechanism if present 12 Reinstall the secondary terminal block onto the breaker midcover terminal block m...

Page 3: ... operation Check that the Remote Close is wired correctly as shown in Figure 5 Check that all connectors are properly seated Check for blown fuses Check that the voltage applied to the Remote Close is within the specified range Remote Charge Switch Secondary D1sconnect Block Draw Out Only Rem Chrg Rem Motor Terminal Block Remote Remote Chrg lnd Chrg Op 8 Close Close 17 33 35 36 34 16 C l c c Q i i...

Page 4: ...aintenance Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser s purposes the matter should be referred to the GE Company GE Electrical Distribution Control General Electric Company 41 WoodfordAve Plainville CT 06062 G 62838 0397 1997 General Electric Company w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Reviews: