Introduction

The  Shunt  Trip  and  Shunt  Trip  with  Lockout  accessories,
shown in Figure 1, can be installed in  800–4000  ampere frame
Power  Break®  II  circuit breakers. These  accessories  allow  the
breaker to be tripped electrically from a remote location.
In addition to providing a  trip signal to the breaker,  the Shunt
Trip  accessories  can  be  set  up  to  interact  with  other  Power
Break II accessories,  when used  with  a  MicroVersaTrip  Plus™
or  MicroVersaTrip  PM™  Trip  Unit.  DIP switches  on the  rear
of  the  breaker  Trip  Unit  can  configure  the  Shunt  Trip
accessories to activate  a  Bell  Alarm–Alarm Only accessory  or  a
Bell  Alarm  with  Lockout  accessory  when  a  shunt  trip  occurs.
The  Accessory  Configuration  section  below  describes  how  this
can be done. If the breaker  is equipped with  a  Power+™ Trip
Unit, it is configured so that only protection trips will  activate  a
Bell Alarm–Alarm Only or Bell Alarm with Lockout.
The  catalog  numbers for  the Shunt  Trip  and  Shunt  Trip  with
Lockout for 480 and 600 Vac are listed in Table  1.  Voltage and
current  ratings  in  Table  1  are  given  at  the  input  of  the
transformer. The  voltage and current ratings of the input  to the
accessory  are  equal  to  that  of  the  120  Vac  version  of  the
accessory. Table 2  lists these ratings.

Operation

Apply  control voltage  to the primary of the  supplied  step-down
transformer. The  secondary  of  the  transformer  is  connected  to
terminals 31  and  32  of the terminal  strip  on the  right  side  of
the breaker.

WARNING:

 

480  Vac  and  600  Vac  Shunt  Trip  accessories

must be used with the supplied step-down transformer.

AVERTISSEMENT:

 Les modules de déclenchement shunt 480

Vac  et  600  Vac  doivent  être  utilisés  avec  le  transformateur
abaisseur de tension qui est fourni.

The  Shunt  Trip  or  Shunt  Trip  with  Lockout  will  cause  the
circuit breaker  to trip when the control voltage  is  greater  than
55%  of the rated  ac  value.  Control  power  to  the  Shunt  Trip
must  be  removed  before  the  breaker  can  be  closed.  Control
power to the Shunt  Trip  with  Lockout  must  be  removed  for  a
minimum of 0.25 second before the breaker can be closed.

Figure 1. Shunt Trip with Lockout

Catalog

Number

Voltage

Rating

Peak Inrush

Current,  mA

Nominal RMS

Current,  mA

SPST480

480  Vac

375

21

SPST600

600  Vac

300

17

SPSTL480

480  Vac

750

20

SPSTL600

600  Vac

600

16

Rated for 50/60 Hz. Rating is 120  Vac without step-down
transformer.

Peak inrush current is present fo r 2–6 ms after activation. This
number is provided so that fuses and supplies can be chosen
appropriately.

Table 1. Catalog numbers and voltages for the Shunt Trip and Shunt

Trip with Lockout.

Accessory

Voltage

Rating

Peak Inrush

Current, A

Nominal RMS

Current,  mA

Shunt Trip

120  Vac

1.5

85

Shunt Trip/

Lockout

120  Vac

3

80

Table 2. Voltage and current ratings for the 120 Vac Shunt Trip and

Shunt Trip with Lockout.

Installation

WARNING:

 Before installing any accessories, turn the breaker

OFF

, disconnect it from all voltage sources,  and  discharge the

charging springs.

AVERTISSEMENT:

  Avant  d’installer  tout  accessoire,  mettre

le disjoncteur en position 

OFF

, le déconnecter de toute tension

d’alimentation, et décharger les ressorts d’armement.

The  Shunt  Trip  or  Shunt  Trip  with  Lockout  is installed in  the
accessory compartment through the front of the circuit breaker  in
the position shown in Figure 2.

g

Power Break

®

 II Circuit Breaker

Accessories

Shunt Trip and Shunt Trip with Lockout
480 & 600 Vac

                                                               

GEH–6519B

Courtesy of NationalSwitchgear.com

Summary of Contents for SPST480

Page 1: ...480 Vac et 600 Vac doivent être utilisés avec le transformateur abaisseur detension qui est fourni The Shunt Trip or Shunt Trip with Lockout will cause the circuit breaker to trip when the control voltage is greater than 55 of the rated ac value Control power to the Shunt Trip must be removed before the breaker can be closed Control power to the Shunt Trip with Lockout must be removed for a minimu...

Page 2: ... 480 Vac and 600 Vac Shunt Trip accessories mustbeused with the supplied step down transformer AVERTISSEMENT Les modules de déclenchement shunt 480 Vac et 600 Vac doivent être utilisés avec le transformateur abaisseur detension qui est fourni Catalog Number Control Voltage Primary Connections Secondary Connections 9T58K0042 480 V H1 H4 X1 X2 9T58K0062 600 V H1 H4 X1 X3 A jumper must be placed from...

Page 3: ...ve the trim plate 2 Loosenthefour 10 32 screws at thecorner of the breaker cover Remove thecover from the breaker face 3 Pull the Trip Unit locking lever to the right then hold the Trip Unit near the battery cover and lift it straight out of thebreaker 4 Refer to Figure 4 and Table 4 to determine the switches to bechanged 5 Push in the appropriate Enable or Disable side of the switch 6 Confirm all...

Page 4: ...ck that the Shunt Trip with Lockout control power is applied at greater than 55 of the rated ac voltage Check that the accessory is completely inserted re insert if necessary Note that an otherwise unpowered Trip Unit is powered by an energized Shunt Trip accessory Check that the Shunt Trip with Lockout accessory is completely inserted 4 The breaker will not close manually when the Shunt Trip or S...

Reviews: