CHAPTER 6: SETPOINTS
S4 CONTROLS
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–127
OUTPUT RELAY 3 to 6
Range: Do Not Operate, Operate
Default: Do Not Operate
Any or all of the output relays 3 to 6 can be selected to operate upon Breaker Failure
detection. The selection of relay outputs operation is available no matter whether the
Latched Alarm
,
Alarm
, or
Trip
function is selected.