Remote Position Sensor Mounted
Remote Position Sensor Mounted
on Reciprocating Actuator
on Rotary Actuator
35
Installation and Set Up
Remote Position Sensor
Figure 19
SVI II AP Remote Position Sensor Installation
Table 5
Remote Position Sensor Turnbuckle Length
Actuator Size
Stroke
Turnbuckle Length
6 and 10
0.5 - 0.8"
(12.7 - 20.32 mm)
1.25"
(31.75 mm)
10
0.5 - 0.8"
(12.7 - 20.32 mm)
1.25"
(31.75 mm)
10
>0.8 – 1.5"
(20.32 - 41.5 mm)
1.25"
(31.75 mm)
16
0.5 - 0.8"
(12.7 - 20.32 mm)
2.90"
(73.66 mm)
16
>0.8 – 1.5"
(20.32 - 41.5 mm)
2.90"
(73.66 mm)
16
>1.5 – 2.5"
(41.5 - 63.5 mm)
2.90"
(73.66 mm)
23
0.5 - 0.8"
(12.7 - 20.32 mm)
5.25"
(133.35 mm)
23
>0.8 – 1.5"
(20.32 - 41.5 mm)
5.25"
(133.35 mm)
23
>1.5 – 2.5"
(41.5 - 63.5 mm)
5.25"
(133.35 mm)
4. Remove the M8 cover-retention screw of the RMS and unscrew the cover to
gain access to the terminal strip.