52
GE Oil & Gas
ValVue SVI II AP Quick Start
Configuration
Use the procedures that follow to: calibrate, tune, view configuration data and
status messages for the SVI II AP. Observe all warnings as the valve moves
during these procedures.
WARNING
These procedures can cause the valve to move. Before
proceeding be sure the valve is isolated from the process.
Keep hands clear from moving parts.
NOTE
All calibration and configuration procedures are described
using an SVI II AP with pushbuttons and display and ValVue
software.
Configuration with Pushbuttons
Prior to changing the SVI II AP configuration, check the existing configuration.
Viewing Configuration Data
To view SVI II AP configuration data:
1. Access the VIEW DATA menu from the MANUAL menu by pressing the
+
button.
2. In the VIEW DATA menu, press
*
to examine the configuration.
3. Press
+
to scroll through and observe the factory configuration.
4. Press
+
until MANPOS appears.
5. Select with
*
.
6. When the adjustment screen appears stroke the valve open by h
down. The rate of set point change is slow to begin, but increases speed while
the + is pressed.
7. Stroke the valve to several values
8. Verify the action is as desired.
9. Press
+
to move to the
SETUP
menu.
10. In the
SETUP
menu press the
*
button to access the
CONFIGuration
menu.
11. In the
CONFIG
menu set the configuration parameters.
12. When in
CONFIGure
or
CALIBrate
, pressing
*
changes values.
13. Return to
NORMAL
mode. The valve moves to the value set by the current
calibrator.
14. Stroke the valve through its range to verify that the movement is as desired.
Summary of Contents for SVI II AP-2
Page 6: ...GE Oil Gas SVI II AP Quick Start Guide 6 ...
Page 10: ...10 GE Oil Gas ValVue SVI II AP Quick Start This page intentionally left blank ...
Page 64: ...64 GE Oil Gas ValVue SVI II AP Quick Start This page intentionally left blank ...
Page 90: ...90 GE Oil Gas ValVue SVI II AP Quick Start Spare Parts ...
Page 91: ...91 Specifications and Spare Parts ...