57
Check Out,
Calibration
Auto Tune
This process takes 3 to 10 minutes and strokes the valve in large and small steps
to set the PID parameters for best positioning response.
WARNING
DO NOT perform STOPS while the valve is controlling the
process.
DO NOT perform Auto Tune while the valve is controlling the
process.
To auto tune the SVI II AP:
1. Press
*
to begin the autoTUNE procedure.
As autoTUNE proceeds, numerical messages display, indicating the
procedure is working.
2. When autoTUNE is complete,
TUNE
appears.
3. Press
+
repeatedly until
SETUP
appears.
4. Press
* t
o return to SETUP menu;
CALIB
appears.