GE Multilin
T35 Transformer Protection System
5-25
5 SETTINGS
5.2 PRODUCT SETUP
5
d) NETWORK
As outlined in the previous section, when using more than one Ethernet port, configure each to belong to a different net-
work or subnet using the IP addresses and mask.
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
NETWORK 1(3)
The
PRT1 (2, 3) GOOSE ENABLED
setting provides the ability to disable/enable GOOSE transmission from the port.
PRT2 REDUNDANCY
is available when the hardware has multiple ports (modules T, U, and V). It determines if ports 2 and 3
operate in redundant or independent mode. In non-redundant mode, port 2 and 3 operate independently with their own
MAC and IP address. In redundant mode, port 2 and 3 use the port 2 MAC and IP address, port 3 is in standby mode and
monitors its link to the Multilink switch, and when port 2 detects a problem with the link then communication switches to port
3 until the link returns. Reboot is required when using the redundancy option.
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, and HTTP protocols. Each
network protocol has a setting for the TCP/UDP port number. These settings are used only in advanced network configura-
tions and should normally be left at their default values, but may be changed if required (for example, to allow access to
multiple UR-series relays behind a router). By setting a different
TCP/UDP PORT NUMBER
for a given protocol on each UR-
series relay, the router can map the relays to the same external IP address. The client software (EnerVista UR Setup, for
example) must be configured to use the correct port number if these settings are used.
NETWORK PORT 1
PRT1 IP ADDRESS:
127.0.0.1
Range: Standard IPV4 address format
MESSAGE
PRT1 SUBNET IP MASK:
255.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT1 GWY IP ADDRESS:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT1 GOOSE ENABLED:
Enabled
Range: Enabled, Disabled
NETWORK PORT 2
PRT2 IP ADDRESS:
127.0.0.1
Range: Standard IPV4 address format
MESSAGE
PRT2 SUBNET IP MASK:
255.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT2 GWY IP ADDRESS:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT2 REDUNDANCY:
No
Range: No, Yes
MESSAGE
PRT2 GOOSE ENABLED:
Enabled
Range: Enabled, Disabled
NETWORK PORT 3
PRT3 IP ADDRESS:
127.0.0.1
Range: Standard IPV4 address format
MESSAGE
PRT3 SUBNET IP MASK:
255.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT3 GWY IP ADDRESS:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT3 GOOSE ENABLED:
Enabled
Range: Enabled, Disabled
Summary of Contents for T35 UR Series
Page 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Page 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...