GE Multilin
T35 Transformer Protection System
5-39
5 SETTINGS
5.2 PRODUCT SETUP
5
The main menu for the IEC 61850 server configuration is shown below.
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
SERVER CONFIGURATION
The
IED NAME
and
LD INST
settings represent the MMS domain name (IEC 61850 logical device) where all IEC/MMS logical
nodes are located. Valid characters for these values are upper and lowercase letters, numbers, and the underscore (_)
character, and the first character in the string must be a letter. This conforms to the IEC 61850 standard. The
LOCATION
is a
variable string and can be composed of ASCII characters. This string appears within the PhyName of the LPHD node.
The
IEC/MMS TCP PORT NUMBER
setting allows the user to change the TCP port number for MMS connections. The
INCLUDE
NON-IEC DATA
setting determines whether or not the “UR” MMS domain will be available. This domain contains a large num-
ber of UR-series specific data items that are not available in the IEC 61850 logical nodes. This data does not follow the IEC
61850 naming conventions. For communications schemes that strictly follow the IEC 61850 standard, this setting should be
“Disabled”.
When a 0 value is involved in a change, the changes to the
IEC/MMS TCP PORT NUMBER
setting take effect when the
T35 is restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
The
SERVER SCANNING
feature should be set to “Disabled” when IEC 61850 client/server functionality is not required. IEC
61850 has two modes of functionality: GOOSE/GSSE inter-device communication and client/server communication. If the
GOOSE/GSSE functionality is required without the IEC 61850 client server feature, then server scanning can be disabled
to increase CPU resources. When server scanning is disabled, there will be not updated to the IEC 61850 logical node sta-
tus values in the T35. Clients will still be able to connect to the server (T35 relay), but most data values will not be updated.
This setting does not affect GOOSE/GSSE operation.
Changes to the
IED NAME
setting,
LD INST
setting, and GOOSE dataset will not take effect until the T35 is restarted.
SERVER
CONFIGURATION
IED NAME: IECDevice
Range: up to 32 alphanumeric characters
MESSAGE
LD INST: LDInst
Range: up to 32 alphanumeric characters
MESSAGE
LOCATION: LPHD DC PHV-
Nam Location
Range: up to 80 alphanumeric characters
MESSAGE
ALTITUDE:
Range: 0 to 10,0000 m in steps of 1 m
MESSAGE
LONGITUDE:
Range: -180.000 to 180.000 deg in steps of 0.001 de
MESSAGE
LATITUDE:
Range: -90.000 to 90.000 deg in steps of 0.001 deg
MESSAGE
IEC/MMS TCP PORT
NUMBER:
102
Range: 0 to 65535 in steps of 1
MESSAGE
INCLUDE NON-IEC
DATA: Enabled
Range: Disabled, Enabled
MESSAGE
SERVER SCANNING:
Disabled
Range: Disabled, Enabled
NOTE
NOTE
Summary of Contents for T35 UR Series
Page 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Page 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...