GE Multilin
T35 Transformer Protection System
5-51
5 SETTINGS
5.2 PRODUCT SETUP
5
PTP DOMAIN NUMBER
•
This setting should be set to the domain number of the grandmaster-capable clock(s) to be synchronized to. A network
may support multiple time distribution domains, each distinguished with a unique domain number. More commonly,
there is a single domain using the default domain number zero.
•
This setting applies to all of the relay’s PTP capable ports.
PTP VLAN PRIORITY
•
This setting selects the value of the priority field in the 802.1Q VLAN tag in request messages issued by the relay’s
peer delay mechanism. In compliance with PP the default VLAN priority is 4, but it is recommended that in accordance
with PTP it be set to 7.
•
Depending on the characteristics of the device to which the relay is directly linked, VLAN Priority may have no effect.
•
This setting applies to all of the relay’s PTP capable ports.
PTP VLAN ID
•
This setting selects the value of the ID field in the 802.1Q VLAN tag in request messages issued by the relay’s peer
delay mechanism. It is provided in compliance with PP. As these messages have a destination address that indicates
they are not to be bridged, their VLAN ID serves no function, and so may be left at its default value.
•
Depending on the characteristics of the device to which the relay is directly linked, VLAN ID may have no effect.
•
This setting applies to all of the relay’s PTP capable ports.
PORT 1 ... 3 FUNCTION
•
While this port setting is selected to disabled, PTP is disabled on this port. The relay does not generate or listen to
PTP messages on this port.
PORT 1 ... 3 PATH DELAY ADDER
•
The time delivered by PTP is advanced by the time value in this setting prior to the time being used to synchronize the
relay’s real time clock. This is to compensate to the extent practical for time delivery delays not compensated for in the
network. In a fully compliant PP network, the peer delay and the processing delay mechanisms compensate for all the
delays between the grandmaster and the relay. In such networks, this setting should be zero.
•
In networks containing one or more switches and/or clocks that do not implement both of these mechanisms, not all
delays are compensated, so the time of message arrival at the relay will be later than the time indicated in the mes-
sage. This setting can be used to approximately compensate for this delay. However, as the relay is not aware of net-
work switching that dynamically changes the amount of uncompensated delay, there is no setting that will always
completely correct for uncompensated delay. A setting can be chosen that will reduce worst-case error to half of the
range between minimum and maximum uncompensated delay, if these values are known.
PORT 1 ... 3 PATH DELAY ASYMMETRY
•
This setting corresponds to “delayAsymmetry” in PTP, which is used by the peer delay mechanism to compensate for
any difference in the propagation delay between the two directions of a link. Except in unusual cases, the two fibers are
of essentially identical length and composition, so this setting should be set to zero.
•
In unusual cases where the length of the link is different in different directions, this setting should be set to the number
of nanoseconds the Ethernet propagation delay to the relay is longer than the mean of path propagation delays to and
from the relay. For instance, if it is known say from the physical length of the fibers and the propagation speed in the
fibers that the delay from the relay to the Ethernet switch it is connected to is 9 000 ns and the that the delay from the
switch to the relay is 11 000 ns, then the mean delay is 10 000 ns, and the path delay asymmetry is 11000 - 10000 =
+1000 ns.
Summary of Contents for T35 UR Series
Page 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Page 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...