5-61
5 SETTINGS
5.2 PRODUCT SETUP
5
Refer to the
LED indicators
section in chapter 4 for additional information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the
LED 1 TYPE
setting is “Self-
Reset” (the default setting), the LED illumination will track the state of the selected LED operand. If the
LED 1 TYPE
setting is
“Latched”, the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a communica-
tions channel, or from any programmed operand, even if the LED operand state de-asserts.
See the figure in the
Control Groups
section of the
Control Elements
section later in this chapter for an example of group
activation.
5.2.12 USER-PROGRAMMABLE SELF TESTS
For user-programmable self-tests for CyberSentry, use the
Setup > Security > Supervisory
menu instead.
PATH: SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE SELF TESTS
Table 5–4: RECOMMENDED SETTINGS FOR USER-PROGRAMMABLE LEDS
SETTING
PARAMETER
SETTING
PARAMETER
LED 1 operand
SETTING GROUP ACT 1
LED 13 operand
Off
LED 2 operand
SETTING GROUP ACT 2
LED 14 operand
Off
LED 3 operand
SETTING GROUP ACT 3
LED 15 operand
Off
LED 4 operand
SETTING GROUP ACT 4
LED 16 operand
Off
LED 5 operand
SETTING GROUP ACT 5
LED 17 operand
Off
LED 6 operand
SETTING GROUP ACT 6
LED 18 operand
Off
LED 7 operand
Off
LED 19 operand
Off
LED 8 operand
Off
LED 20 operand
Off
LED 9 operand
Off
LED 21 operand
Off
LED 10 operand
Off
LED 22 operand
Off
LED 11 operand
Off
LED 23 operand
Off
LED 12 operand
Off
LED 24 operand
Off
USER-PROGRAMMABLE
SELF TESTS
DIRECT RING BREAK
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
MESSAGE
DIRECT DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
MESSAGE
REMOTE DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
FIRST ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
SEC. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
THIRD ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
BATTERY FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
SNTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
IRIG-B FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
PTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
Summary of Contents for T35 UR Series
Page 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Page 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...