GE Multilin
T35 Transformer Protection System
8-13
8 SECURITY
8.2 CYBERSENTRY
8
Security Alarm Settings
b) PASSWORD REQUIREMENTS
See the Password Requirements section earlier.
c) USER ROLES
CyberSentry user roles (Administrator, Engineer, Operator, Supervisor, Observer) limit the levels of access to various UR
device functions. This means the EnerVista software allows for access to functionality based on the user’s logged in role.
Example:
Observer cannot write any settings. The Observer role displays as "None" on the front panel.
The table lists the roles that are supported and their corresponding capabilities.
Table 8–4: PERMISSIONS BY USER ROLE FOR CYBERSENTRY
SETTING NAME
DESCRIPTION / DETAILS
MIN
MAX
DEFAULT UNITS
MINIMUM
PERMISSIONS
Failed
Authentications
A threshold number indicating when an alarm is
set off to indicate too many failed authentication
attempts
0
(disabled)
99
3
-
Administrator
Firmware lock
A Boolean value indicating if the device can
receive a firmware upgrade. If Yes and a
firmware upgrade attempt is made, the device
alarm activates. If No the device alarm does not
activate. On each firmware upgrade this setting
goes back to the default.
No
Yes
Yes
-
Administrator
Settings lock
A Boolean value indicating if the device can
accept any settings changes. If Yes and a
settings change attempt is made, the device
alarm activates. If No, the device alarm does not
activate.
No
Yes
Yes
-
Supervisor
(Administrator if
Supervisor has
been disabled)
Roles
Administrator
Engineer
Operator
Supervisor
Observer
UR Setup Software Tree Menu
Complete Access
Complete access
except for
CyberSentry
Security
Command
Menu
Authorizes
writing
This role is active
by default
Settings
|------------
Product Setup
|--------------- Security (CyberSentry)
RW
R
R
R
R
|--------------- Supervisory
see table notes
R
R
see table notes
R
|--------------- Display Properties
RW
RW
R
R
R
|---------------
Clear relay records
(settings)
RW
RW
R
R
R
|--------------- Communications
RW
RW
R
R
R
|--------------- Modbus user map
RW
RW
R
R
R
|--------------- Real Time Clock
RW
RW
R
R
R
|--------------- Oscillography
RW
RW
R
R
R
|--------------- Data Logger
RW
RW
R
R
R
|--------------- Demand
RW
RW
R
R
R
|---------------
User Programmable
LEDs
RW
RW
R
R
R
|---------------
User Programmable
self test
RW
RW
R
R
R
|--------------- Control Pushbuttons
RW
RW
R
R
R
|---------------
User programmable
Pushbuttons
RW
RW
R
R
R
|--------------- Flex states
RW
RW
R
R
R
|---------------
User definable dis-
plays
RW
RW
R
R
R
|--------------- Direct I/O
RW
RW
R
R
R
Summary of Contents for T35 UR Series
Page 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Page 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...