GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
User Manual
TLE Series 160 - 500 UL S2B
COMMANDS 1 SCREEN
Allows the user to execute UPS
operation commands.
Rectifier
Rectifier ON
Rectifier switching ON command.
Rectifier RESET
Rectifier restore command.
Reserved for the
GE Service Center
.
Led Rectifier status
Indicates the Rectifier’s status: ON = lit OFF = turned Off
Inverter
Inverter ON
Inverter switching ON command.
NOTE !
When eBoost™ Operation Mode or IEMi Operation Mode is enabled, control of
Inverter status and selection of the feed path is done autonomously by the
UPS control logic.
Therefore, Inverter ON / Inverter OFF commands are disabled when eBoost™
Operation Mode
or IEMi Operation Mode is enabled.
Inverter OFF
Inverter switching OFF command.
This command is also used as “
EPO - Emergency Power Off”
reset after the contact closing.
NOTE !
Inverter OFF
command is disabled when eBoost™ Operation Mode or IEMi
Operation Mode
is enabled.
Led Inverter status
It indicates the Inverter status:
ON / OFF / Pre-charge / Pre-charge completed / Soft-start