Critical Power
Modifications reserved
Page 32/146
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
User Manual
TLE Series 600 & 800 CE S1
Fixing of the UPS cabinet
TLE Series 600 & 800
on the floor
Fig. 5.4.1.8 TLE Series 600 & 800
–
Fixing of the UPS cabinet on the floor
The UPS cabinet is free standing and normally does not require to be bolted to the floor.
The UPS cabinet can be fixed however to the floor by bolting it with the supporting blocks to the
floor.
Fig. 5.4.1-9 TLE Series 600
–
UPS cabinet floor fixing points
TLES_UL_750-1000
_S1_UPS fixing_01
Power Section cabinet
In/Out Section cabinet
750
mm
/ 2
9.5
3
"
60 m
m
/
2.3
7
"
865
mm
/ 3
4.0
6
"
54 mm / 2.13 "
TLES_600_S1_UPS fixing_02
FRONTAL SIDE
700 mm / 27.56 "
700 mm / 27.56 "
1275 mm / 50.20 "
3000 mm / 143.50 "
60 mm / 2.37 "
100 mm / 3.94 "
60 mm / 2.37 "
Ø 13.5
mm
/ 0
.53 "