3

DEH41188 Installation Instructions

 

 

Effective November 2016

Installation Instructions for TMQV
Circuit Breakers and Molded Case Switches

 

Figure  2. Circuit  Breaker  Mounting  Bolt  Drilling  Plans

Figure  3. Circuit  Breaker  

Esutcheon

 

Dimensions

2-4.  If an optional terminal end cover is to be installed  with  the 

circuit breaker (usually  line end only),  it must  be positioned  before  

cable is connected  to terminals .

 CAUTION

WHEN ALUMINUM CONDUCTORS ARE USED, THE APPLICATION OF 

A SUITABLE JOINT COMPOUND IS RECOMMENDED TO REDUCE THE 

POSSIBILITY OF TERMINAL OVERHEATING. TERMINAL OVERHEATING CAN 

CAUSE NUISANCE TRIPPING AND DAMAGE TO THE CIRCUIT BREAKER.

2-5.  After  mounting  the circuit breaker,  line and load terminals  and 

accessory  leads should  be connected .  (See  accessory  schematic  

diagram on side  of circuit breaker.)

ote :

N

If terminal shield  or interphase  barriers are to be installed  on the circuit 

breaker,  install them  after the terminals  are connected .

2913

I

.188 (4.78 mm) Dia. Hole for

Access to Push-to-Trip

Line

End

2.313

(58.75)

2-6.  If required,  install terminal shield  on circuit breaker cover with  

mounting  screws  provided .

2-7.  If required,  install an interphase  barrier by sliding  barrier into 

dovetail grooves  between  terminals .

2-8.  After  the circuit breaker is installed,  check  all mounting  hard-

ware and terminal connecting  hardware for correct torque loading. 

Torque  values for line/load terminals  are given in Tables  1, 2, and 3 

and on the circuit breaker nameplate.

Table  1.  Terminal  Types

Terminal 

Catalog #

 

(Not orderable) 

Terminal 

Body 

Material

Screw 

Head Type

AWG 

Wire 

Range

Metric 

Wire 

Range

Wire 

Type

Torque 

Value, Lb. 

in.(N.m)

3TA225FD

Aluminum 3/16 Socket

Hex

#4-4/0 25-95

Cu/Al

120 (13.6)

3TA225CVK

Aluminum 5/16 Socket 

Hex

#6-300 16-150 Cu/Al

275 (31)

2TA225CVK

Aluminum 5/16 Socket 

Hex

#6-300 16-150 Cu/Al

275 (31)

3TA100FD

Aluminum Slotted

#14-1/0 2.5-5.0 Cu/Al

See Table 2

3T100FB

Steel

Slotted

#14-1/0 2.5-50

Cu/Al

See Table 2

3T150FB

Stainless 

Steel

Slotted

#4-4/0 25-95

Cu 

Only

See Table 2

3TA150F3K

Aluminum 5/32 Socket 

Hex

#14-2

2.5-25

Cu/Al

70 (7.9)

3TA150F6K

Aluminum 3/32 Socket 

Hex

#14-6

2.5-10

Cu/Al

25 (2.8)

Note: Terminal wire connectors are UL listed for standard wire sizes as defined in UL 486A 

and UL486B.

Package of Three

Individual Terminal Identified as TA225FD1
Package of Two

Table  2.  Terminal  Torque  Values  for  Slotted  Head

Metric Wire 

Range

Torque Value N.m

AWG Wire Range

Torque Value, 

Lb.-In.

2.5-6

3.96

#14-#10

35 

10

4.52

#8

40

16-25

5.09

#6-#4

45

35-95

5.65

#3-4/0

50

Summary of Contents for TMQV

Page 1: ... Page Introduction 2 Installation 2 Manual Operation 4 Inspection and Field Testing 4 Effective November 2016 DEH41188 Installation Instrucitons Installation Instructions for TMQV Circuit Breakers and Molded Case Switches ...

Page 2: ...factory Where local codes and standards per mit and UL listing is not required internal accessories can be field installed Accessory installation should be done before the circuit breaker is mounted and connected Mounting hardware and unmounted terminations where required are supplied in separate packages 2 1 Make sure that the circuit breaker is suitable for the installation by comparing nameplat...

Page 3: ...install an interphase barrier by sliding barrier into dovetail grooves between terminals 2 8 After the circuit breaker is installed check all mounting hard ware and terminal connecting hardware for correct torque loading Torque values for line load terminals are given in Tables 1 2 and 3 and on the circuit breaker nameplate Table 1 Terminal Types Terminal Catalog Not orderable Terminal Body Materi...

Page 4: ... PLATES OR MOLDED PARTS 4 1 Remove dust dirt soot grease or moisture from the surface of the circuit breaker using a lint free dry cloth brush or vacuum cleaner Do not blow debris into circuit breaker If contamination is found look for the source and eliminate the problem 4 2 Switch circuit breaker to ON and OFF several times to be sure that the mechanical linkages are free and do not bind If mech...

Page 5: ...5 ...

Page 6: ......

Reviews: