background image

4

Effective November 2016

Installation Instructions for TMQV

Circuit Breakers and Molded Case Switches

3. Manual Operation

Manual operation of the circuit breaker is controlled by the circuit 

breaker handle and the PUSH-TO-TRIP button. The circuit breaker 

handle has three indicated positions, two of which are shown on 

the cover with raised lettering to indicate ON and OFF. On the slid-

ing handle barrier, ON, OFF, and trip are also shown by a color-coded 

strip for each circuit breaker handle position: red for ON, white for 

tripped, and green for OFF. On the sliding handle barrier, ON/OFF is 

also shown with the international symbols I/0 (See Fig. 4.)

Figure 4.  Circuit Breaker Manual Controls.

Circuit Breaker Reset

After tripping, the circuit breaker is reset by moving the circuit break-

er handle to the extreme OFF position.

ote: 

N

In the event of a thermal trip, the circuit breaker cannot be reset until 

the thermal element cools.

PUSH-TO-TRIP Button

The PUSH-TO-TRIP button checks the tripping function and is used 

to periodically exercise the operating mechanism.

4. Inspection and Field Testing

TMQV molded case circuit breakers are designed to provide years 

of almost maintenance-free operation. The following procedure 

describes how to inspect and test a circuit breaker in service.

Inspection

Circuit breakers in service should be inspected periodically.  The 

inspection should include the following checks 4-1 thru 4-7.

 WARNING

BEFORE INSPECTING THE CIRCUIT BREAKER IN AN ELECTRICAL 

SYSTEM, MAKE SURE THE CIRCUIT BREAKER IS SWITCHED TO THE OFF 

POSITION AND THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE 

PERFORMED.  SPECIAL ATTENTION SHOULD BE PAID TO REVERSE FEED 

APPLICATIONS  TO ENSURE NO VOLTAGE IS PRESENT. THE VOLTAGES IN 

ENERGIZED EQUIPMENT CAN  CAUSE INJURY OR DEATH.

 CAUTION

MAKE SURE THAT CLEANING AGENTS OR SOLVENTS USED TO CLEAN 

THE CIRCUIT BREAKER ARE SUITABLE FOR THE JOB. SOME  COMMERCIAL 

CLEANING AGENTS WILL DAMAGE THE NAME PLATES OR MOLDED 

PARTS.

4-1. Remove dust, dirt, soot, grease, or moisture from the surface 

of the circuit breaker using a lint-free dry cloth, brush, or vacuum 

cleaner. Do not blow debris into circuit breaker. If contamination is 

found, look for the source and eliminate the problem.
4-2. Switch circuit breaker to ON and OFF several times to be sure 

that the mechanical linkages are free and do not bind. If mechanical 

linkages are not free, replace circuit breaker.
4-3. Press the PUSH-TO-TRIP button to mechanically trip the circuit 

breaker. Trip, reset, and switch circuit breaker ON several times. If 

mechanism does not reset each time the circuit breaker is tripped, 

replace the circuit
4-4. Check base, cover, and operating handle for cracks, chipping, 

and discoloration. Circuit breakers should be replaced if cracks or 

severe discoloration is found.
4-5. Check terminals and connectors for looseness or signs of over-

heating. Overheating will show as discoloration, melting, or blister-

ing of conductor insulation, or as pitting or melting of conductor sur-

faces due to arcing. If there is no evidence of overheating or loose-

ness, do not disturb or tighten the connections. If there is evidence 

of overheating, terminations should be cleaned or replaced. Before 

re-energizing the circuit breaker, all terminations and cable should be 

refurbished to the condition when originally installed.

4-6. Check circuit breaker mounting hardware. Tighten if necessary.

4-7. Check area where circuit breaker is installed for any safety haz-

ards, including personal safety and fire hazards. Exposure to certain 

types of chemicals can cause deterioration of electrical connections.

Field Testing

Any field testing should be done in accordance with applicable 

NEMA Standards.

DEH41188 Installation Instructions

 

 

 

 

 

 

GE

41 Woodford Ave.

Plainville, CT 06062

© 2016 General Electric Company

 

 

 

 

 

 

   

 

 

Information provided is subject to change without notice. Please verify all details with GE.

All values are design or typical values when measured under laboratory conditions, and GE makes no warranty

or guarantee, express or implied, that such performance will be obtained under end-use conditions.

Summary of Contents for TMQV

Page 1: ... Page Introduction 2 Installation 2 Manual Operation 4 Inspection and Field Testing 4 Effective November 2016 DEH41188 Installation Instrucitons Installation Instructions for TMQV Circuit Breakers and Molded Case Switches ...

Page 2: ...factory Where local codes and standards per mit and UL listing is not required internal accessories can be field installed Accessory installation should be done before the circuit breaker is mounted and connected Mounting hardware and unmounted terminations where required are supplied in separate packages 2 1 Make sure that the circuit breaker is suitable for the installation by comparing nameplat...

Page 3: ...install an interphase barrier by sliding barrier into dovetail grooves between terminals 2 8 After the circuit breaker is installed check all mounting hard ware and terminal connecting hardware for correct torque loading Torque values for line load terminals are given in Tables 1 2 and 3 and on the circuit breaker nameplate Table 1 Terminal Types Terminal Catalog Not orderable Terminal Body Materi...

Page 4: ... PLATES OR MOLDED PARTS 4 1 Remove dust dirt soot grease or moisture from the surface of the circuit breaker using a lint free dry cloth brush or vacuum cleaner Do not blow debris into circuit breaker If contamination is found look for the source and eliminate the problem 4 2 Switch circuit breaker to ON and OFF several times to be sure that the mechanical linkages are free and do not bind If mech...

Page 5: ...5 ...

Page 6: ......

Reviews: