GE Multilin
745 Transformer Management Relay
5-67
5 SETPOINTS
5.6 S4 ELEMENTS
5
c) NEGATIVE SEQUENCE INSTANTANEOUS OVERCURRENT
PATH: SETPOINTS
ÖØ
S4 ELEMENTS
ÖØ
NEG SEQ OC
ÖØ
W1(3) NEG SEQ INST OC
•
W1(3) NEG SEQ INST OC PICKUP
: Enter the level of negative sequence current (in units of relay nominal current)
above which the Winding 1(3) Negative Sequence Instantaneous Overcurrent element will pickup and start the delay
timer.
•
W1(3) NEG SEQ INST OC DELAY
: Enter the time that the negative sequence current must remain above the pickup
level before the element operates.
Figure 5–28: NEGATIVE SEQUENCE IOC SCHEME LOGIC
W1 NEG SEQ INST OC
[ENTER] for more
W1 NEG SEQ INST OC
FUNCTION: Disabled
Range: Enabled, Disabled
W1 NEG SEQ INST OC
TARGET: Latched
Range: Self-Reset, Latched, None
W1 NEG SEQ INST OC
PICKUP: 10.00 x CT
Range: 0.05 to 20.00 x CT in steps of 0.01
W1 NEG SEQ INST OC
DELAY: 0 ms
Range: 0 to 60000 ms in steps of 1
W1 NEG SEQ INST OC
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to 16, Output Rly 2 to
8, SelfTest Rly, Vir Outpt 1 to 5, Disabled
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE