GE Multilin
745 Transformer Management Relay
6-11
6 ACTUAL VALUES
6.3 A2 METERING
6
b) DEMAND DATA CLEAR
PATH: ACTUAL VALUES
ÖØ
A2 METERING
ÖØ
DEMAND
Ö
DEMAND DATA CLEAR
To clear all maximum demand data, set
CLEAR MAX DEMAND DATA
to "Yes". The last date and time that the demand data
were cleared are also displayed. If the date has never been programmed, the default values shown above appear.
c) CURRENT DEMAND
PATH: ACTUAL VALUES
ÖØ
A2 METERING
ÖØ
DEMAND
ÖØ
W1(3) CURRENT DEMAND
The current demand for Winding 1 Phases A through C are displayed in these messages. The maximum current demand,
the phase in which it occurred, and the date and time it occurred are also shown. If the date has never been programmed,
the default values shown above appear.
These messages are repeated for Windings 2 and 3.
6.3.7 AMBIENT TEMPERATURE
PATH: ACTUAL VALUES
ÖØ
A2 METERING
ÖØ
AMBIENT TEMPERATURE
Ambient temperature is monitored via an RTD connected to the 745.
DEMAND DATA CLEAR
[ENTER] for more
CLEAR MAX DEMAND
DATA: No
DATE OF LAST CLEAR:
Jan 01 1996
TIME OF LAST CLEAR:
00:00:00.000
W1 CURRENT DEMAND
[ENTER] for more
CLEAR MAX DEMAND
DATA: No
W1 PHASE A CURRENT
DEMAND:
0 A
W1 PHASE B CURRENT
DEMAND:
0 A
W1 PHASE C CURRENT
DEMAND:
0 A
MAXIMUM W1 DEMAND:
0 A in phase A
MAXIMUM W1 DEMAND
DATE: Jan 01 1996
MAXIMUM W1 DEMAND
TIME: 00:00:00.000
AMBIENT TEMP
[ENTER] for more
AMBIENT TEMPERATURE:
0°C
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
ESCAPE
ð
ð