6-20
745 Transformer Management Relay
GE Multilin
6.6 TARGET AND FLASH MESSAGES
6 ACTUAL VALUES
6
All conditions listed in the following table cause a target message to be generated.
6.6.3 FLASH MESSAGES
Flash messages are warning, error, or general information messages displayed in response to certain key presses. The
length of time these messages remain displayed can be programmed in
S1 745 SETUP
ÖØ
PREFERENCES
ÖØ
FLASH MES-
SAGE TIME
. The factory default flash message time is 4 seconds.
Table 6–2: SELF-TEST ERROR INTERPRETATION
MESSAGE
SEVERITY
CAUSE
EEPROM Memory
major
This error is caused by detection of corrupted location in the 745 data memory which cannot be
self-corrected. Errors that can be automatically corrected are not indicated. Any function of the
745 is susceptible to maloperate from this failure.
Flexlogic Eqn
major
This error is caused when an error in FlexLogic™ is detected. No feature of the 745 that is
controlled by FlexLogic will operate when this failure occurs. Programming correct FlexLogic
equations will remove this error.
DSP Processor
major
This error is caused when communications with the internal digital signal processor is lost.
Most of the monitoring capability of the 745 (including all measurement of current) will be lost
when this failure occurs.
Bad Xfmr Settings
major
This error is caused when the 745 determines that the transformer configuration programmed
via setpoints does not correspond to a realistic physical system.
Logic Power Out
minor
This error is caused by failure of the +32 V DC power supply used to power dry contacts of
logic inputs. Logic inputs using internal power are affected by this failure. This may be caused
by an external connection which shorts this power supply to ground.
Analog Output
minor
This error is caused by failure of the +32 V DC power supply used to power analog outputs.
Analog output currents are affected by this failure.
Not Calibrated
minor
This error message appears when the 745 determines that it has not been calibrated. Although
the relay is fully functional, the accuracy of measured input values (e.g. currents and line
voltage) as well as generated outputs (e.g. analog outputs) is not likely to be within those
specified for the relay.
Real-Time Clock
minor
This error is caused when the 745 detects that the real-time clock is not running. Under this
condition, the 745 will not be able to maintain the current time and date. This would normally
occur if backup battery power for the clock is lost and control power is removed from the 745.
Even if control power is restored, the clock will not operate until the time and/or date are
programmed via the
S1 745 SETUP
ÖØ
CLOCK
menu.
Emulation Software
minor
This error is caused by development software being loaded in the relay.
Int Temperature
minor
This error is caused by the detection of unacceptably low (less than –40°C) or high (greater
than +85°C) temperatures detected inside the unit
IRIG-B Failure
minor
This error is caused when the IRIG-B signal type selected does not match the format code
being injected into the IRIG-B terminals.
Access Denied
minor
This error is caused when the passcode is entered incorrectly three times in a row from either
the front panel or any of the communication ports. This error may be removed by entering the
correct passcode.
Ambnt temperature
minor
This error is caused when ambient temperature is out of range.(–50 to 250°C inclusive).
ADJUSTED VALUE
HAS BEEN STORED
This flash message is displayed in response to pressing
while on a setpoint
message with a numerical value. The edited value had to be adjusted to the nearest
multiple of the step value before it was stored.
COMMAND IS BEING
EXECUTED
This flash message is displayed in response to executing a command at a command
message. Entering Yes at a command message will display the message
ARE YOU
SURE?
. Entering Yes again will perform the requested command, and display this
flash message.
DEFAULT MESSAGE
HAS BEEN ADDED
This flash message is displayed in response to pressing the decimal key, followed by
twice, on any setpoint or actual value message except those in the subgroup
S1 745 SETUP
ÖØ
DEFAULT MESSAGES
.
DEFAULT MESSAGE
HAS BEEN REMOVED
This flash message is displayed in response to pressing the decimal key, followed by
twice, on one of the selected default messages in the subgroup
S1 745 SETUP
ÖØ
DEFAULT MESSAGES
.
ENTER
ENTER
ENTER