7-56
745 Transformer Management Relay
GE Multilin
7.4 MODBUS MEMORY MAP
7 COMMUNICATIONS
7
F60
16 bits
ACTIVE SETPOINT GROUP
0000 0000 0000 0000
0 = Group 1
0000 0000 0000 0001
1 = Group 2
0000 0000 0000 0010
2 = Group 3
0000 0000 0000 0011
3 = Group 4
F61
16 bits
TIMER OPERATE FLAGS
xxxx xxxx xxxx xxx1
Timer 1
(0 = Not Operated, 1 = Operated)
xxxx xxxx xxxx xx1x
Timer 2
(0 = Not Operated, 1 = Operated)
xxxx xxxx xxxx x1xx
Timer 3
(0 = Not Operated, 1 = Operated)
xxxx xxxx xxxx 1xxx
Timer 4
(0 = Not Operated, 1 = Operated)
xxxx xxxx xxx1 xxxx
Timer 5
(0 = Not Operated, 1 = Operated)
xxxx xxxx xx1x xxxx
Timer 6
(0 = Not Operated, 1 = Operated)
xxxx xxxx x1xx xxxx
Timer 7
(0 = Not Operated, 1 = Operated)
xxxx xxxx 1xxx xxxx
Timer 8
(0 = Not Operated, 1 = Operated)
xxxx xxx1 xxxx xxxx
Timer 9
(0 = Not Operated, 1 = Operated)
xxxx xx1x xxxx xxxx
Timer 10
(0 = Not Operated, 1 = Operated)
F62
16 bits
FLEXLOGIC EQUATION (NO
GATES)
Format F47 for tokens 0000 01111 and greater - i.e. no gates)
F63
16 bits
VOLTAGE INPUT PARAMETERS
0000 0000 0000 0000
0 = W1 Van
0000 0000 0000 0001
1 = W1 Vbn
0000 0000 0000 0010
2 = W1 Vcn
0000 0000 0000 0011
3 = W1 Vab
0000 0000 0000 0100
4 = W1 Vbc
0000 0000 0000 0101
5 = W1 Vca
0000 0000 0000 0110
6 = W2 Van
0000 0000 0000 0111
7 = W2 Vbn
0000 0000 0000 1000
8 = W2 Vcn
0000 0000 0000 1001
9 = W2 Vab
0000 0000 0000 1010
10 = W2 Vbc
0000 0000 0000 1011
11 = W2 Vca
0000 0000 0000 1100
12 = W3 Van
0000 0000 0000 1101
13 = W3 Vbn
0000 0000 0000 1110
14 = W3 Vcn
0000 0000 0000 1111
15 = W3 Vab
0000 0000 0001 0000
16 = W3 Vbc
0000 0000 0001 0001
17 = W3 Vca
F64
16 bits
HARMONIC PARAMETERS
0000 0000 0000 0000
0 = 2nd
0000 0000 0000 0001
1 = 2nd+5th
Table 7–6: 745 DATA FORMATS (Sheet 17 of 25)
CODE
APPLICABLE BITS
DEFINITION
F65
16 bits
TRACE MEMORY CHANNEL
0000 0000 0000 0000
0 = W1 Ia
0000 0000 0000 0001
1 = W1 Ib
0000 0000 0000 0010
2 = W1 Ic
0000 0000 0000 0011
3 = W2 Ia
0000 0000 0000 0100
4 = W2 Ib
0000 0000 0000 0101
5 = W2 Ic
0000 0000 0000 0110
6 = W3 Ia
0000 0000 0000 0111
7 = W3 Ib
0000 0000 0000 1000
8 = W3 Ic
0000 0000 0000 1001
9 = W1/2 Ig
0000 0000 0000 1010
10 = W2/3 Ig
0000 0000 0000 1011
11 = Voltage
0000 0000 0000 1100
12 = Logic Inputs
0000 0000 0000 1101
13 = Output Relays
F66
16 bits
OUTPUT OPERATION
0000 0000 0000 0000
0 = Self-resetting
0000 0000 0000 0001
1 = Latched
F67
16 bits
BLOCK OPERATION OF OUTPUTS
xxxx xxxx xxxx xxx1
Output Relay 1 (0 = Allow Operation,
1 = Block Operation)
xxxx xxxx xxxx xx1x
Output Relay 1 (0 = Allow Operation,
1 = Block Operation)
xxxx xxxx xxxx x1xx
Output Relay 1 (0 = Allow Operation,
1 = Block Operation)
xxxx xxxx xxxx 1xxx
Output Relay 1 (0 = Allow Operation,
1 = Block Operation)
xxxx xxxx xxx1 xxxx
Output Relay 1 (0 = Allow Operation,
1 = Block Operation)
xxxx xxxx xx1x xxxx
Output Relay 1 (0 = Allow Operation,
1 = Block Operation)
xxxx xxxx x1xx xxxx
Output Relay 1 (0 = Allow Operation,
1 = Block Operation)
xxxx xxxx 1xxx xxxx
Output Relay 1 (0 = Allow Operation,
1 = Block Operation)
F68
16 bits
RESET TIME
0000 0000 0000 0000
0 = Instantaneous
0000 0000 0000 0001
1 = Linear
F69
16 bits
PLAYBACK MEMORY CHANNEL
0000 0000 0000 0000
0 = W1 Ia
0000 0000 0000 0001
1 = W1 Ib
0000 0000 0000 0010
2 = W1 Ic
0000 0000 0000 0011
3 = W2 Ia
0000 0000 0000 0100
4 = W2 Ib
0000 0000 0000 0101
5 = W2 Ic
0000 0000 0000 0110
6 = W3 Ia
0000 0000 0000 0111
7 = W3 Ib
0000 0000 0000 1000
8 = W3 Ic
0000 0000 0000 1001
9 = W1/2 Ig
0000 0000 0000 1010
10 = W2/3 Ig
0000 0000 0000 1011
11 = Voltage
Table 7–6: 745 DATA FORMATS (Sheet 18 of 25)
CODE
APPLICABLE BITS
DEFINITION