7-64
745 Transformer Management Relay
GE Multilin
7.5 DNP COMMUNICATIONS
7 COMMUNICATIONS
7
The following table specifies the default variation for all objects returned by the relay. These are the variations that will be
returned for the object in a response when no specific variation is specified in a request.
7.5.3 DNP POINT LISTS
Notes:
1.
Any detected change in the state of any point will cause the generation of an event object.
DEFAULT VARIATIONS
OBJECT
DESCRIPTION
DEFAULT
VARIATION
1
Binary Input - Single Bit
1
2
Binary Input Change With Time
2
10
Binary Output Status
2
30
16-Bit Analog Input Without Flag
4
32
16-Bit Analog Input Change Without Time
2
POINT LIST FOR:BINARY INPUT (OBJECT 01)
BINARY INPUT CHANGE (OBJECT 02)
INDEX
DESCRIPTION
EVENT CLASS
ASSIGNED TO
NOTES
0
Logic Input 1 Operated
Class 1
Note 1
1
Logic Input 2 Operated
Class 1
Note 1
2
Logic Input 3 Operated
Class 1
Note 1
3
Logic Input 4 Operated
Class 1
Note 1
4
Logic Input 5 Operated
Class 1
Note 1
5
Logic Input 6 Operated
Class 1
Note 1
6
Logic Input 7 Operated
Class 1
Note 1
7
Logic Input 8 Operated
Class 1
Note 1
8
Logic Input 9 Operated
Class 1
Note 1
9
Logic Input 10 Operated
Class 1
Note 1
10
Logic Input 11 Operated
Class 1
Note 1
11
Logic Input 12 Operated
Class 1
Note 1
12
Logic Input 13 Operated
Class 1
Note 1
13
Logic Input 14 Operated
Class 1
Note 1
14
Logic Input 15 Operated
Class 1
Note 1
15
Logic Input 16 Operated
Class 1
Note 1
16
Output Relay 1 Energized
Class 1
Note 1
17
Output Relay 2 Energized
Class 1
Note 1
18
Output Relay 3 Energized
Class 1
Note 1
19
Output Relay 4 Energized
Class 1
Note 1
20
Output Relay 5 Energized
Class 1
Note 1
21
Output Relay 6 Energized
Class 1
Note 1
22
Output Relay 7 Energized
Class 1
Note 1
23
Output Relay 8 Energized
Class 1
Note 1
24
Self-Test Relay Energized
Class 1
Note 1
25
Setpoint Group 1 Active
Class 1
Note 1
26
Setpoint Group 2 Active
Class 1
Note 1
27
Setpoint Group 3 Active
Class 1
Note 1
28
Setpoint Group 4 Active
Class 1
Note 1