GE Multilin
F35 Multiple Feeder Protection System
5-159
5 SETTINGS
5.6 GROUPED ELEMENTS
5
Figure 5–61: GROUND IOC1 SCHEME LOGIC
5.6.7 NEGATIVE SEQUENCE CURRENT
a) MAIN MENU
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
NEGATIVE SEQUENCE CURRENT
For additional information on the negative sequence time overcurrent curves, see the
Inverse Time Overcurrent Curves
section earlier.
NEGATIVE SEQUENCE
CURRENT
NEG SEQ TOC1
MESSAGE
NEG SEQ TOC2
MESSAGE
NEG SEQ IOC1
MESSAGE
NEG SEQ IOC2
SETTING
GROUND IOC1
FUNCTION:
Enabled = 1
SETTING
GROUND IOC1
SOURCE:
IG
GROUND IOC1
BLOCK:
Off = 0
FLEXLOGIC OPERANDS
GROUND IOIC DPO
GROUND IOC1 OP
SETTING
SETTING
IG
PICKUP
GROUND IOC1
PICKUP:
RUN
GROUND IOC1 PICKUP
DELAY:
SETTINGS
GROUND IOC1 RESET
DELAY:
t
PKP
t
RST
827037A5.VSD
AND
GROUND IOC1 PKP