B-22
F35 Multiple Feeder Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Security (Read/Write Setting)
3295
Supervisor Alphanumeric Password Setting
---
---
---
F202
(none)
Security (Read Only)
329F
Supervisor Alphanumeric Password Status
0 to 1
---
1
F102
0 (Disabled)
Security (Read/Write)
32A0
Supervisor Alphanumeric Password Entry
---
---
---
F202
(none)
Security (Read/Write Setting)
32AA
Engineer Alphanumeric Password Setting
---
---
---
F202
(none)
Security (Read Only)
32B4
Engineer Alphanumeric Password Status
0 to 1
---
1
F102
0 (Disabled)
Security (Read/Write)
32B5
Engineer Alphanumeric Password Entry
---
---
---
F202
(none)
Security (Read/Write Setting)
32BF
Operator Alphanumeric Password Setting
---
---
---
F202
(none)
Security (Read Only)
32C9
Operator Alphanumeric Password Status
0 to 1
---
1
F102
0 (Disabled)
Security (Read/Write)
32CA
Operator Alphanumeric Password Entry
---
---
---
F202
(none)
Security (Read/Write Setting)
32D4
Observer Alphanumeric Password Setting
---
---
---
F202
(none)
Security (Read Only)
32DE
Observer Alphanumeric Password Status
0 to 1
---
1
F102
0 (Disabled)
Security (Read/Write)
32DF
Observer Alphanumeric Password Entry
---
---
1
F202
(none)
Security (Read Only)
32E9
Reserved for password settings of future roles (63 items)
0 to 65535
---
1
F001
0
3328
Security Status Indicator
0 to 65535
---
1
F618
0
Security (Read/Write Setting)
3329
Session Lockout
0 to 99
---
1
F001
3
332A
Session Lockout Period
0 to 9999
min
1
F001
3
332B
Load Factory Defaults
0 to 1
---
1
F126
0 (No)
332C
Syslog Server IP Address
0 to 4294967295
---
1
F003
0
332E
Syslog Server Port Number
1 to 65535
---
1
F001
514
Security Supervisory (Read/Write Setting)
3331
Device Authentication Enable
0 to 1
---
1
F126
1 (Yes)
3332
Supervisor Role Enable
0 to 1
---
1
F102
0 (Disabled)
3333
Lock Relay
0 to 1
---
1
F102
0 (Disabled)
3334
Factory Service Mode Enable
0 to 1
---
1
F102
0 (Disabled)
3335
Failed Authentication Alarm Enable
0 to 1
---
1
F102
1 (Enabled)
3336
Firmware Lock Alarm
0 to 1
---
1
F102
1 (Enabled)
3337
Settings Lock Alarm
0 to 1
---
1
F102
1 (Enabled)
3338
Bypass Access
0 to 3
---
1
F628
0 (Disabled)
333A
Serial Inactivity Timeout
1 to 9999
---
1
F001
1
Security Command (Read/Write Command)
3350
Operator Logoff
0 to 1
---
1
F126
0 (No)
3351
Engineer Logoff
0 to 1
---
1
F126
0 (No)
3352
Administrator Logoff
0 to 1
---
1
F126
0 (No)
3353
Clear Security Data
0 to 1
---
1
F126
0 (No)
Security Reserved Modbus Registers (Read/Write)
3360
Address 0x3360 reserved for serial login (20 items)
0 to 9999
---
1
F001
3
3374
Address 0x3374 reserved for serial logout
0 to 9999
---
1
F001
3
Security Reserved Modbus Registers (Read Only)
3375
Address 0x3374 reserved for serial logout
0 to 5
---
1
F617
3 (Engineer)
Table B–10: MODBUS MEMORY MAP (Sheet 14 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR F35 Series
Page 10: ...x F35 Multiple Feeder Protection System GE Multilin TABLE OF CONTENTS ...
Page 366: ...5 238 F35 Multiple Feeder Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 426: ...10 12 F35 Multiple Feeder Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 454: ...A 28 F35 Multiple Feeder Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 620: ...F 12 F35 Multiple Feeder Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 630: ...H 8 F35 Multiple Feeder Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 640: ...x F35 Multiple Feeder Protection System GE Multilin INDEX ...