GE Multilin
F35 Multiple Feeder Protection System
B-27
APPENDIX B
B.4 MEMORY MAPPING
B
3B1B
...Repeated for Field Shared Input 4
3B24
...Repeated for Field Shared Input 5
3B2D
...Repeated for Field Shared Input 6
3B36
...Repeated for Field Shared Input 7
3B3F
...Repeated for Field Shared Input 8
3B48
...Repeated for Field Shared Input 9
3B51
...Repeated for Field Shared Input 10
3B5A
...Repeated for Field Shared Input 11
3B63
...Repeated for Field Shared Input 12
3B6C
...Repeated for Field Shared Input 13
3B75
...Repeated for Field Shared Input 14
3B7E
...Repeated for Field Shared Input 15
3B87
...Repeated for Field Shared Input 16
Field Unit Contact Outputs (Read/Write Setting) (8 modules)
3B90
Field Contact Output 1 ID (6 items)
---
---
---
F205
"FCO U /OUT"
3BB4
Field Output 1 Operate (6 items)
0 to 4294967295
---
1
F300
0
3BC0
Field Output 1 Seal In (6 items)
0 to 4294967295
---
1
F300
0
3BCC
Field Output 1 Events (6 items)
0 to 1
---
1
F102
1 (Enabled)
3BD2
...Repeated for Field Contact Output 2
3C14
...Repeated for Field Contact Output 3
3C56
...Repeated for Field Contact Output 4
3C98
...Repeated for Field Contact Output 5
3CDA
...Repeated for Field Contact Output 6
3D1C
...Repeated for Field Contact Output 7
3D5E
...Repeated for Field Contact Output 8
Field Unit Latching Outputs (Read/Write Setting) (8 modules)
3DC7
Field Latching Output 1 ID
0 to 1
---
1
F205
"FLO Ux /LO"
3DCD
Field Latching Output 1 Open
0 to 4294967295
---
1
F300
0
3DCF
Field Latching Output 1 Close
0 to 4294967295
---
1
F300
0
3DD1
Field Latching Output 1 Events
0 to 1
---
1
F102
1 (Enabled)
3DD2
Field Latching Output 1 Reserved (2 items)
0 to 1
---
1
F001
0
3DD4
...Repeated for Field Latching Output 2
3DE1
...Repeated for Field Latching Output 3
3DEE
...Repeated for Field Latching Output 4
3DFB
...Repeated for Field Latching Output 5
3E08
...Repeated for Field Latching Output 6
3E15
...Repeated for Field Latching Output 7
3E22
...Repeated for Field Latching Output 8
Field Unit Shared Outputs (Read/Write Setting) (16 modules)
3E30
Field Shared Output 1 ID
0 to 65535
---
1
F205
"SO 1"
3E36
Field Shared Output 1 Operate
0 to 4294967295
---
1
F300
0
3E38
Field Shared Output 1 Unit Dest 1
0 to 8
---
1
F256
0 (None)
3E39
Field Shared Output 1 Channel Dest 1
1 to 15
---
1
F001
1
3E3A
Field Shared Output 1 Unit Dest 2
0 to 8
---
1
F256
0 (None)
3E3B
Field Shared Output 1 Channel Dest 2
1 to 15
---
1
F001
1
3E3C
Field Shared Output 1 Events
0 to 1
---
1
F102
1 (Enabled)
3E3D
...Repeated for Field Shared Output 2
3E4A
...Repeated for Field Shared Output 3
3E57
...Repeated for Field Shared Output 4
3E64
...Repeated for Field Shared Output 5
3E71
...Repeated for Field Shared Output 6
3E7E
...Repeated for Field Shared Output 7
3E8B
...Repeated for Field Shared Output 8
3E98
...Repeated for Field Shared Output 9
Table B–10: MODBUS MEMORY MAP (Sheet 19 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR F35 Series
Page 10: ...x F35 Multiple Feeder Protection System GE Multilin TABLE OF CONTENTS ...
Page 366: ...5 238 F35 Multiple Feeder Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 426: ...10 12 F35 Multiple Feeder Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 454: ...A 28 F35 Multiple Feeder Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 620: ...F 12 F35 Multiple Feeder Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 630: ...H 8 F35 Multiple Feeder Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 640: ...x F35 Multiple Feeder Protection System GE Multilin INDEX ...