10-8
F35 Multiple Feeder Protection System
GE Multilin
10.3 UNINSTALL AND CLEAR FILES AND DATA
10 MAINTENANCE
10
10.3UNINSTALL AND CLEAR FILES AND DATA
10.3.1 UNINSTALL AND CLEAR FILES AND DATA
The unit can be decommissioned by turning off power to the unit and disconnecting the wires to it.
Files can be cleared after uninstalling the EnerVista software or UR device, for example to comply with data security regu-
lations.
On the computer, settings files can identified by the .urs extension. To clear the current settings file, create a default set-
tings file, write it to the relay, then delete all other .urs files. For the existing installation, upgrading the firmware overwrites
the flash memory. Other files can be in standard formats, such as COMTRADE or .csv.
You cannot erase directly the flash memory, but all records and settings in that memory can be deleted. Do this using the
SETTINGS
PRODUCT SETUP
CLEAR RELAY RECORDS
command.