B.4 MEMORY MAPPING
B
PRP Status (Read Only)
4363
Total Received Port A
0 to 4294967295
---
1
F003
0
4365
Total Received Port B
0 to 4294967295
---
1
F003
0
4367
Total Mismatches Port A
0 to 4294967295
---
1
F003
0
4369
Total Mismatches Port B
0 to 4294967295
---
1
F003
0
436B
Total Errors
0 to 4294967295
---
1
F003
0
IPv4 Route Table (Read/Write Setting) (6 modules)
4370
IPv4 Network Route 1 Destination
0 to 4294967295
---
1
F003
2130706433
4372
IPv4 Network Route 1 Netmask
0 to 4294967295
---
1
F003
4278190080
4374
IPv4 Network Route 1 Gateway
0 to 4294967295
---
1
F003
2130706433
4376
...Repeated for Route 2
437C
...Repeated for Route 3
4382
...Repeated for Route 4
4388
...Repeated for Route 5
438E
...Repeated for Route 6
Installation (Read/Write Setting)
43E0
Relay Programmed State
0 to 1
---
1
F133
0 (Not
Programmed)
43E1
Relay Name
---
---
---
F202
“Relay-1”
User Programmable Self Tests (Read/Write Setting)
4441
User Programmable Detect Ring Break Function
0 to 1
---
1
F102
1 (Enabled)
4442
User Programmable Direct Device Off Function
0 to 1
---
1
F102
1 (Enabled)
4443
User Programmable Remote Device Off Function
0 to 1
---
1
F102
1 (Enabled)
4444
User Programmable First Ethernet Fail Function
0 to 1
---
1
F102
0 (Disabled)
4445
User Programmable Secondary Ethernet Fail Function
0 to 1
---
1
F102
0 (Disabled)
4446
User Programmable Battery Fail Function
0 to 1
---
1
F102
1 (Enabled)
4447
User Programmable SNTP Fail Function
0 to 1
---
1
F102
1 (Enabled)
4448
User Programmable IRIG-B Fail Function
0 to 1
---
1
F102
1 (Enabled)
4449
User Programmable Ethernet Switch Fail Function
0 to 1
---
1
F102
1 (Enabled)
444A
Process Bus Failure Operand
0 to 4294967295
---
1
F300
0
444C
PTP Fail Function
0 to 1
---
1
F102
1 (Enabled)
444D
User Programmable Third Ethernet Fail Function
0 to 1
---
1
F102
0 (Disabled)
444E
User Programmable SFP Fail Function
0 to 1
---
1
F102
0 (Disabled)
CT Settings (Read/Write Setting) (6 modules)
4480
Phase CT 1 Primary
1 to 65000
A
1
F001
1
4481
Phase CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
4482
Ground CT 1 Primary
1 to 65000
A
1
F001
1
4483
Ground CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
4484
...Repeated for CT Bank 2
4488
...Repeated for CT Bank 3
448C
...Repeated for CT Bank 4
4490
...Repeated for CT Bank 5
4494
...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (6 modules)
4500
Phase VT 1 Connection
0 to 1
---
1
F100
0 (Wye)
4501
Phase VT 1 Secondary
25 to 240
V
0.1
F001
664
4502
Phase VT 1 Ratio
1 to 24000
:1
1
F060
1
4504
Auxiliary VT 1 Connection
0 to 6
---
1
F166
1 (Vag)
4505
Auxiliary VT 1 Secondary
25 to 240
V
0.1
F001
664
4506
Auxiliary VT 1 Ratio
1 to 24000
:1
1
F060
1
4508
...Repeated for VT Bank 2
4510
...Repeated for VT Bank 3
4518
...Repeated for VT Bank 4
4520
...Repeated for VT Bank 5
Table B–10: MODBUS MEMORY MAP (Sheet 25 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR F35 Series
Page 10: ...x F35 Multiple Feeder Protection System GE Multilin TABLE OF CONTENTS ...
Page 366: ...5 238 F35 Multiple Feeder Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 426: ...10 12 F35 Multiple Feeder Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 454: ...A 28 F35 Multiple Feeder Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 620: ...F 12 F35 Multiple Feeder Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 630: ...H 8 F35 Multiple Feeder Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 640: ...x F35 Multiple Feeder Protection System GE Multilin INDEX ...