GE Multilin
C70 Capacitor Bank Protection and Control System
5-195
5 SETTINGS
5.7 CONTROL ELEMENTS
5
Figure 5–100: VT FUSE FAIL SCHEME LOGIC
827093AM.CDR
FUSE
FAIL
FAULT
AND
AND
AND
AND
SET
RESET
Reset-dominant
Latch
AND
AND
AND
AND
AND
OR
OR
OR
OR
Latch
SET
Reset-dominant
RESET
Function
SETTING
Disabled = 0
Enabled = 1
SOURCE 1
V_2
V_1
I_1
COMPARATORS
Run
V_1 < 0.05 pu
Run
V_2 > 0.1 pu
Run
I_1 > 0.075 pu
Run
V_1 < 0.80 pu
Run
I_1 < 0.05 pu
SRC1 50DD OP
FLEXLOGIC OPERANDS
2 cycles
20 cycles
SRC1 VT FUSE FAIL OP
FLEXLOGIC OPERANDS
SRC1 VT FUSE FAIL DPO
SRC1 VT FUSE FAIL VOL LOSS
FLEXLOGIC OPERAND
TIMER
OPEN POLE OP
The OPEN POLE OP operand is applicable
to the D60, L60, and L90 only.