GE Multilin
C70 Capacitor Bank Protection and Control System
B-13
APPENDIX B
B.4 MEMORY MAPPING
B
21A7
Breaker flashover 1 side 1 source
0 to 5
---
1
F167
0 (SRC 1)
21A8
Breaker flashover 1 side 2 source
0 to 6
---
1
F211
0 (None)
21A9
Breaker flashover 1 status closed A
0 to 65535
---
1
F300
0
21AA
Breaker flashover 1 status closed B
0 to 65535
---
1
F300
0
21AB
Breaker flashover 1 status closed C
0 to 65535
---
1
F300
0
21AC
Breaker flashover 1 voltage pickup level
0 to 1.5
pu
0.001
F001
850
21AD
Breaker flashover 1 voltage difference pickup level
0 to 100000
V
1
F060
1000
21AF
Breaker flashover 1 current pickup level
0 to 1.5
pu
0.001
F001
600
21B0
Breaker flashover 1 pickup delay
0 to 65.535
s
0.001
F001
100
21B1
Breaker flashover 1 supervision phase A
0 to 65535
---
1
F300
0
21B2
Breaker flashover 1 supervision phase B
0 to 65535
---
1
F300
0
21B3
Breaker flashover 1 supervision phase C
0 to 65535
---
1
F300
0
21B4
Breaker flashover 1 block
0 to 65535
---
1
F300
0
21B5
Breaker flashover 1 events
0 to 1
---
1
F102
0 (Disabled)
21B6
Breaker flashover 1 target
0 to 2
---
1
F109
0 (Self-Reset)
21B7
Reserved (4 items)
---
---
---
F001
0
21BB
...Repeated for breaker flashover 2
0 to 99999999
kA
2
-cyc
1
F060
0
Passwords Unauthorized Access (Read/Write Command)
2230
Reset Unauthorized Access
0 to 1
---
1
F126
0 (No)
Remote double-point status inputs (read/write setting registers)
2620
Remote double-point status input 1 device
1 to 32
---
1
F001
1
2621
Remote double-point status input 1 item
0 to 128
---
1
F156
0 (None)
2622
Remote double-point status input 1 name
1 to 64
---
1
F205
"Rem Ip 1"
2628
Remote double-point status input 1 events
0 to 1
---
1
F102
0 (Disabled)
2629
... Repeated for double-point status input 2
2632
... Repeated for double-point status input 3
263B
... Repeated for double-point status input 4
2644
... Repeated for double-point status input 5
IEC 61850 GGIO5 configuration (read/write setting registers)
26B0
IEC 61850 GGIO5 uinteger input 1 operand
---
---
---
F612
0
26B1
IEC 61850 GGIO5 uinteger input 2 operand
---
---
---
F612
0
26B2
IEC 61850 GGIO5 uinteger input 3 operand
---
---
---
F612
0
26B3
IEC 61850 GGIO5 uinteger input 4 operand
---
---
---
F612
0
26B4
IEC 61850 GGIO5 uinteger input 5 operand
---
---
---
F612
0
26B5
IEC 61850 GGIO5 uinteger input 6 operand
---
---
---
F612
0
26B6
IEC 61850 GGIO5 uinteger input 7 operand
---
---
---
F612
0
26B7
IEC 61850 GGIO5 uinteger input 8 operand
---
---
---
F612
0
26B8
IEC 61850 GGIO5 uinteger input 9 operand
---
---
---
F612
0
26B9
IEC 61850 GGIO5 uinteger input 10 operand
---
---
---
F612
0
26BA
IEC 61850 GGIO5 uinteger input 11 operand
---
---
---
F612
0
26BB
IEC 61850 GGIO5 uinteger input 12 operand
---
---
---
F612
0
26BC
IEC 61850 GGIO5 uinteger input 13 operand
---
---
---
F612
0
26BD
IEC 61850 GGIO5 uinteger input 14 operand
---
---
---
F612
0
26BE
IEC 61850 GGIO5 uinteger input 15 operand
---
---
---
F612
0
26BF
IEC 61850 GGIO5 uinteger input 16 operand
---
---
---
F612
0
IEC 61850 received integers (read only actual values)
26F0
IEC 61850 received uinteger 1
0 to 4294967295
---
1
F003
0
26F2
IEC 61850 received uinteger 2
0 to 4294967295
---
1
F003
0
26F4
IEC 61850 received uinteger 3
0 to 4294967295
---
1
F003
0
26F6
IEC 61850 received uinteger 4
0 to 4294967295
---
1
F003
0
26F8
IEC 61850 received uinteger 5
0 to 4294967295
---
1
F003
0
26FA
IEC 61850 received uinteger 6
0 to 4294967295
---
1
F003
0
26FC
IEC 61850 received uinteger 7
0 to 4294967295
---
1
F003
0
26FE
IEC 61850 received uinteger 8
0 to 4294967295
---
1
F003
0
Table B–9: MODBUS MEMORY MAP (Sheet 6 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT