GE Multilin
C70 Capacitor Bank Protection and Control System
B-33
APPENDIX B
B.4 MEMORY MAPPING
B
7F20
...Repeated for Neutral Overvoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules)
7F30
Auxiliary Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7F31
Auxiliary Overvoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7F32
Auxiliary Overvoltage 1 Pickup
0 to 3
pu
0.001
F001
300
7F33
Auxiliary Overvoltage 1 Pickup Delay
0 to 600
s
0.01
F001
100
7F34
Auxiliary Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7F35
Auxiliary Overvoltage 1 Block
0 to 65535
---
1
F300
0
7F36
Auxiliary Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7F37
Auxiliary Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7F38
Reserved (8 items)
0 to 65535
---
1
F001
0
7F40
...Repeated for Auxiliary Overvoltage 2
7F50
...Repeated for Auxiliary Overvoltage 3
Frequency (Read Only)
8000
Tracking Frequency
---
Hz
---
F001
0
Breaker Failure (Read/Write Grouped Setting) (2 modules)
8600
Breaker Failure 1 Function
0 to 1
---
1
F102
0 (Disabled)
8601
Breaker Failure 1 Mode
0 to 1
---
1
F157
0 (3-Pole)
8602
Breaker Failure 1 Source
0 to 5
---
1
F167
0 (SRC 1)
8603
Breaker Failure 1 Amp Supervision
0 to 1
---
1
F126
1 (Yes)
8604
Breaker Failure 1 Use Seal-In
0 to 1
---
1
F126
1 (Yes)
8605
Breaker Failure 1 Three Pole Initiate
0 to 65535
---
1
F300
0
8606
Breaker Failure 1 Block
0 to 65535
---
1
F300
0
8607
Breaker Failure 1 Phase Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
8608
Breaker Failure 1 Neutral Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
8609
Breaker Failure 1 Use Timer 1
0 to 1
---
1
F126
1 (Yes)
860A
Breaker Failure 1 Timer 1 Pickup
0 to 65.535
s
0.001
F001
0
860B
Breaker Failure 1 Use Timer 2
0 to 1
---
1
F126
1 (Yes)
860C
Breaker Failure 1 Timer 2 Pickup
0 to 65.535
s
0.001
F001
0
860D
Breaker Failure 1 Use Timer 3
0 to 1
---
1
F126
1 (Yes)
860E
Breaker Failure 1 Timer 3 Pickup
0 to 65.535
s
0.001
F001
0
860F
Breaker Failure 1 Breaker Status 1 Phase A/3P
0 to 65535
---
1
F300
0
8610
Breaker Failure 1 Breaker Status 2 Phase A/3P
0 to 65535
---
1
F300
0
8611
Breaker Failure 1 Breaker Test On
0 to 65535
---
1
F300
0
8612
Breaker Failure 1 Phase Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
8613
Breaker Failure 1 Neutral Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
8614
Breaker Failure 1 Phase Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
8615
Breaker Failure 1 Neutral Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
8616
Breaker Failure 1 Loset Time
0 to 65.535
s
0.001
F001
0
8617
Breaker Failure 1 Trip Dropout Delay
0 to 65.535
s
0.001
F001
0
8618
Breaker Failure 1 Target
0 to 2
---
1
F109
0 (Self-reset)
8619
Breaker Failure 1 Events
0 to 1
---
1
F102
0 (Disabled)
861A
Breaker Failure 1 Phase A Initiate
0 to 65535
---
1
F300
0
861B
Breaker Failure 1 Phase B Initiate
0 to 65535
---
1
F300
0
861C
Breaker Failure 1 Phase C Initiate
0 to 65535
---
1
F300
0
861D
Breaker Failure 1 Breaker Status 1 Phase B
0 to 65535
---
1
F300
0
861E
Breaker Failure 1 Breaker Status 1 Phase C
0 to 65535
---
1
F300
0
861F
Breaker Failure 1 Breaker Status 2 Phase B
0 to 65535
---
1
F300
0
8620
Breaker Failure 1 Breaker Status 2 Phase C
0 to 65535
---
1
F300
0
8621
...Repeated for Breaker Failure 2
8642
...Repeated for Breaker Failure 3
8663
...Repeated for Breaker Failure 4
8684
...Repeated for Breaker Failure 5
86A5
...Repeated for Breaker Failure 6
Table B–9: MODBUS MEMORY MAP (Sheet 26 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT